14 AWG through 2 AWG THHN/THWN Insulated Singles Wrapped in Moisture-Resistant, Flame-Retardant Paper. 16 AWG Aluminum Bond Wire. UL Listed. 600 Volts. Rated VW-1. Lightweight Aluminum Interlocked Armor.
Southwire Armorlite® Type AC Cable is suitable for use as follows:
Conductor | Ground Wire | ||||||||
No. of Conductors | Size (AWG or kcmil) (mm2) | No. of Strands | Insulation Thickness (mils) (mm) | Size (AWG) | No. of Strands | Nom. OD (mils) (mm) | Nominal Total Weight (lbs/1000') (kgs/km) | Allowable Ampacity | |
610293 |
2
2
|
14 AWG
14 AWG
|
1
1
|
15
0.38
|
50.8
50.8
|
|
468
11.89
|
88
132
|
|
610294 |
3
3
|
14 AWG
14 AWG
|
1
1
|
15
0.38
|
50.8
50.8
|
|
488
12.41
|
108
160
|
|
610296 |
4
4
|
14 AWG
14 AWG
|
1
1
|
15
0.38
|
50.8
50.8
|
|
520
13.22
|
131
194
|
|
553270 |
2
2
|
12 AWG
12 AWG
|
1
1
|
15
0.38
|
50.8
50.8
|
|
501
12.74
|
111
165
|
|
610232 |
3
3
|
12 AWG
12 AWG
|
1
1
|
15
0.38
|
50.8
50.8
|
|
524
13.32
|
136
203
|
|
610297 |
4
4
|
12 AWG
12 AWG
|
1
1
|
15
0.38
|
50.8
50.8
|
|
560
14.24
|
165
246
|
|
610298 |
2
2
|
10 AWG
10 AWG
|
1
1
|
20
0.51
|
50.8
50.8
|
|
555
14.12
|
139
207
|
|
610299 |
3
3
|
10 AWG
10 AWG
|
1
1
|
20
0.51
|
50.8
50.8
|
|
583
14.81
|
180
268
|
|
610300 |
4
4
|
10 AWG
10 AWG
|
1
1
|
|
50.8
50.8
|
|
629
15.98
|
226
336
|
|
890607 |
2
2
|
8 AWG
8 AWG
|
19
19
|
30
0.76
|
50.8
50.8
|
|
780
19.81
|
244
362
|
|
890608 |
3
3
|
8 AWG
8 AWG
|
19
19
|
30
0.76
|
50.8
50.8
|
|
817
20.76
|
315
468
|
|
890691 |
2
2
|
6 AWG
6 AWG
|
19
19
|
30
0.76
|
50.8
50.8
|
|
862
21.89
|
326
486
|
|
890692 |
3
3
|
6 AWG
6 AWG
|
19
19
|
|
50.8
50.8
|
|
905
23.01
|
432
643
|
|
890695 |
3
3
|
4 AWG
4 AWG
|
19
19
|
40
1.02
|
50.8
50.8
|
|
1054
26.79
|
627
934
|
|
890696 |
4
4
|
4 AWG
4 AWG
|
19
19
|
40
1.02
|
50.8
50.8
|
|
1142
29.01
|
798
1187
|
|
553275 |
3
3
|
3 AWG
3 AWG
|
19
19
|
40
1.02
|
|
|
1115
28.33
|
748
1113
|
|
553278 |
4
4
|
3 AWG
3 AWG
|
19
19
|
40
1.02
|
|
|
1209
30.72
|
956
1423
|
|
890698 |
3
3
|
2 AWG
2 AWG
|
19
19
|
40
1.02
|
50.8
50.8
|
|
1184
30.09
|
899
1337
|
|
890699 |
4
4
|
2 AWG
2 AWG
|
19
19
|
40
1.02
|
50.8
50.8
|
|
1286
32.68
|
1155
1718
|
|
Southwire Armorlite® Type AC Cable meets or exceeds the following requirements:
Southwire Armorlite® Type AC Cable is constructed with soft-drawn copper, Type THHN insulated conductors which are individually wrapped with a moisture-resistant, flame-retardant paper covering. Aluminum interlocking armor is applied over the assembly. A 16 AWG aluminum bond wire is placed inside the armor, runs longitudinally and is in intimate contact with the armor for its entire length.