RHINOPOWERTM Type MP-GC mine power feeder cable is a heavy-duty power cable for use in stationary horizontal HV mine power distribution circuits, for permanent or semi-portable applications with power transmission in deep mines, surface mines, open pits, tunnels, in conduit or duct (not to exceed max rated voltage), and suitable for direct burial in wet or dry locations. For vertical drop requirements consult with factory application specialist.
Cond. Size | Conductor Number | Cond. Strands | Diameter Over Conductor (in) (cm) | Insulation Thickness (mils) (mm) | Diameter Over Insulation (in) (cm) | Ground Check Size | Jacket Thickness (mils) (mm) | Approx. OD (in) (cm) | Approx. Weight (lbs/1000') (kgs/km) | |
More Options |
4/0 AWG
4/0 AWG
|
3
3
|
19
19
|
0.474
1.20
|
115
2.92
|
0.738
1.87
|
8
8
|
140
3.56
|
2.120
5.38
|
3838
5712
|
More Options |
350 KCMIL
350 KCMIL
|
3
3
|
855
855
|
0.615
1.56
|
95
2.41
|
0.937
2.38
|
8
8
|
140
3.56
|
2.810
7.14
|
6453
9603
|
* Strand count meets minimum number per ASTM
Cond. Size | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Capacitive Reactance (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | Rated Strength (lbs) (kg) | Min. Bend Radius (in) (cm) | Allowable Ampacity In Air 90C | |
More Options |
4/0 AWG
4/0 AWG
|
0.051
0.08
|
0.065
0.10
|
0.023
0.03
|
0.032
0.05
|
1447
656.35
|
25.4
64.52
|
321
321
|
More Options |
350 KCMIL
350 KCMIL
|
0.031
0.05
|
0.041
0.06
|
0.021
0.03
|
0.031
0.05
|
2394
1085.90
|
33.7
85.60
|
435
435
|
* Ampacities based upon ICEA S-75-381 Table I-1.
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.