RHINOPOWER<sup>TM</sup> Type MP-GC mine power feeder cable is a heavy-duty power cable for use in stationary horizontal HV mine power distribution circuits, for permanent or semi-portable applications with power transmission in deep mines, surface mines, open pits, tunnels, in conduit or duct (not to exceed max rated voltage), and suitable for direct burial in wet or dry locations. For vertical drop requirements consult with factory application specialist.
Cond. Size (AWG/Kcmil) | Conductor Number | Cond. Strands | Diameter Over Conductor (in) (cm) | Insulation Thickness (mils) (mm) | Diameter Over Insulation (in) (cm) | Ground (No. x AWG) | Ground Check Size | Ground Check Strands | Ground Insulation Thickness (mils) (mm) | Inner Jacket Thickness (mils) (mm) | Diameter Over Armor (in) (cm) | Jacket Thickness (mils) (mm) | Approx. OD (in) (cm) | Approx. Weight (lbs/1000') (kgs/km) | |
577276 |
4
4
|
3.0
3.0
|
7
7
|
0.212
0.54
|
90
2.29
|
0.440
1.12
|
|
8
8
|
|
|
|
|
110
2.79
|
1.320
3.35
|
1158
1723
|
580827 |
2
2
|
3.0
3.0
|
7
7
|
0.268
0.68
|
90
2.29
|
0.478
1.21
|
|
8
8
|
|
|
|
|
115
2.92
|
1.565
3.98
|
1686
2509
|
592868 |
1
1
|
3.0
3.0
|
19
19
|
0.298
0.76
|
90
2.29
|
0.506
1.29
|
|
8
8
|
|
|
|
|
110
2.79
|
1.530
3.89
|
1779
2647
|
584648 |
1/0
1/0
|
3.0
3.0
|
19
19
|
0.336
0.85
|
90
2.29
|
0.546
1.39
|
|
8
8
|
|
|
|
|
160
4.06
|
1.630
4.14
|
2149
3198
|
Cond. Size (AWG/Kcmil) | DC Resistance @ 25C (ohms/1000') (ohms/km) | AC Resistance @ 75C (ohms/1000') (ohms/km) | Capacitive Reactance (Mohms x 1000ft) (Mohms x km) | Inductive Reactance (ohms/1000') (ohms/km) | Rated Strength (lbs) (kg) | Max Pull Tension (lbs) (kg) | Min. Bend Radius (in) (cm) | In Air Ampacity @ 60C (amps) | In Air Ampacity @ 75C (amps) | In Air Ampacity @ 90C (amps) | In Air Ampacity @ 105C (amps) | Raceway Ampacity @ 75C (amps) | Raceway Ampacity @ 90C (amps) | |
577276 |
4
4
|
0.258
0.38
|
0.325
0.48
|
0.049
0.07
|
0.038
0.06
|
285
129.27
|
|
15.8
40.13
|
|
|
122
122
|
|
|
|
580827 |
2
2
|
0.162
0.24
|
0.204
0.30
|
0.039
0.06
|
0.035
0.05
|
453
205.48
|
|
18.7
47.50
|
|
|
159
159
|
|
|
|
592868 |
1
1
|
0.128
0.19
|
0.162
0.24
|
0.036
0.05
|
0.034
0.05
|
572
259.45
|
|
18.3
46.48
|
|
|
184
184
|
|
|
|
584648 |
1/0
1/0
|
0.102
0.15
|
0.128
0.19
|
0.033
0.05
|
0.033
0.05
|
722
327.49
|
|
19.5
49.53
|
|
|
211
211
|
|
|
|