RHINOPOWER<sup>TM</sup> Type MP-GC mine power feeder cable is a heavy-duty power cable for use in stationary horizontal HV mine power distribution circuits, for permanent or semi-portable applications with power transmission in deep mines, surface mines, open pits, tunnels, in conduit or duct (not to exceed max rated voltage), and suitable for direct burial in wet or dry locations. For vertical drop requirements consult with factory application specialist.
Cond. Size (AWG/Kcmil) | Conductor Number | Cond. Strands | Diameter Over Conductor (in) (cm) | Insulation Thickness (mils) (mm) | Diameter Over Insulation (in) (cm) | Ground (No. x AWG) | Ground Check Size | Ground Check Strands | Ground Insulation Thickness (mils) (mm) | Inner Jacket Thickness (mils) (mm) | Diameter Over Armor (in) (cm) | Jacket Thickness (mils) (mm) | Approx. OD (in) (cm) | Approx. Weight (lbs/1000') (kgs/km) | |
579258 |
4/0
4/0
|
3.0
3.0
|
19
19
|
0.474
1.20
|
115
2.92
|
0.738
1.87
|
|
8
8
|
|
|
|
|
140
3.56
|
2.120
5.38
|
3838
5712
|
581812 |
350
350
|
3.0
3.0
|
855
855
|
0.615
1.56
|
95
2.41
|
0.937
2.38
|
|
8
8
|
|
|
|
|
140
3.56
|
2.810
7.14
|
6453
9603
|
Cond. Size (AWG/Kcmil) | DC Resistance @ 25C (ohms/1000') (ohms/km) | AC Resistance @ 75C (ohms/1000') (ohms/km) | Capacitive Reactance (Mohms x 1000ft) (Mohms x km) | Inductive Reactance (ohms/1000') (ohms/km) | Rated Strength (lbs) (kg) | Max Pull Tension (lbs) (kg) | Min. Bend Radius (in) (cm) | In Air Ampacity @ 60C (amps) | In Air Ampacity @ 75C (amps) | In Air Ampacity @ 90C (amps) | In Air Ampacity @ 105C (amps) | Raceway Ampacity @ 75C (amps) | Raceway Ampacity @ 90C (amps) | |
579258 |
4/0
4/0
|
0.051
0.08
|
0.065
0.10
|
0.023
0.03
|
0.032
0.05
|
1447
656.35
|
|
25.4
64.52
|
|
|
321
321
|
|
|
|
581812 |
350
350
|
0.031
0.05
|
0.041
0.06
|
0.021
0.03
|
0.031
0.05
|
2394
1085.90
|
|
33.7
85.60
|
|
|
435
435
|
|
|
|