SPEC: 45251

CU 600V PVC-Nylon Insulation PVC Jacket THHN/THWN-2. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free

Type TC-ER Power Cable 600Volt Three Conductor Copper, Polyvinyl Chloride (PVC) with nylon layer insulation THHN Polyvinyl Chloride (PVC) Jacket with 1 Bare CU Ground. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free.

Download Category Specifications
PDF Excel Table

Application & Features

Southwire’s 600 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 75°C in wet locations and 90°C in dry locations, 105°C for emergency overload, and 150°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Sunlight Resistant - For Direct Burial - Silicone Free

Specifications

Select a set of products below for more information:
Cond. Size Conductor Number Cond. Strands Diameter Over Conductor (in) (cm) Inner Layer Thickness (mils) (mm) Outer Layer Thickness (mils) (mm) Approx. OD (in) (cm) Copper Weight (lbs/1000') (kgs/km) Approx. Weight (lbs/1000') (kgs/km)
More Options
8 AWG 8 AWG
3.0 3.0
7 7
0.141 0.36
30 0.76
60 1.52
0.640 1.63
186 277
307 457
More Options
6 AWG 6 AWG
3.0 3.0
7 7
0.177 0.45
30 0.76
60 1.52
0.734 1.86
297 442
451 671
More Options
4 AWG 4 AWG
3.0 3.0
7 7
0.225 0.57
40 1.02
60 1.52
0.804 2.04
441 656
618 920
More Options
2 AWG 2 AWG
3.0 3.0
7 7
0.282 0.72
40 1.02
80 2.03
0.986 2.50
702 1045
971 1445
More Options
1 AWG 1 AWG
3.0 3.0
19 19
0.322 0.82
50 1.27
80 2.03
1.116 2.83
864 1286
1180 1756
More Options
1/0 AWG 1/0 AWG
3.0 3.0
19 19
0.361 0.92
50 1.27
80 2.03
1.183 3.00
1069 1591
1406 2092
More Options
2/0 AWG 2/0 AWG
3.0 3.0
19 19
0.405 1.03
50 1.27
80 2.03
1.278 3.25
1326 1973
1689 2514
More Options
3/0 AWG 3/0 AWG
3.0 3.0
19 19
0.456 1.16
50 1.27
80 2.03
1.386 3.52
1699 2528
2100 3125
More Options
4/0 AWG 4/0 AWG
3.0 3.0
19 19
0.512 1.30
50 1.27
80 2.03
1.481 3.76
2109 3139
2603 3874
More Options
250 KCMIL 250 KCMIL
3.0 3.0
37 37
0.558 1.42
60 1.52
80 2.03
1.659 4.21
2469 3674
3091 4600
More Options
350 KCMIL 350 KCMIL
3.0 3.0
37 37
0.661 1.68
60 1.52
110 2.79
1.941 4.93
3438 5116
4186 6229
More Options
500 KCMIL 500 KCMIL
3.0 3.0
37 37
0.789 2.00
60 1.52
110 2.79
2.168 5.51
4884 7268
5733 8532
More Options
600 KCMIL 600 KCMIL
3.0 3.0
61 61
0.865 2.20
70 1.78
110 2.79
2.388 6.07
5820 8661
6784 10096
More Options
750 KCMIL 750 KCMIL
3.0 3.0
61 61
0.968 2.46
70 1.78
110 2.79
2.602 6.61
7277 10829
8562 12742
Cond. Size Conductor Number Min. Bend Radius (in) (cm) Max Pull Tension (lbs) (kg) DC Resistance at 25C (ohms/1000') (ohms/km) AC Resistance at 75C (ohms/1000') (ohms/km) Inductive Reactance (ohms/1000') (ohms/km) Allowable Ampacity Raceway 75C Allowable Ampacity Raceway 90C
More Options
8 AWG 8 AWG
3.0 3.0
2.6 6.60
396 179.62
0.653 0.97
0.786 1.17
0.052 0.08
50 50
55 55
More Options
6 AWG 6 AWG
3.0 3.0
2.9 7.37
629 285.31
0.411 0.61
0.495 0.74
0.051 0.08
65 65
75 75
More Options
4 AWG 4 AWG
3.0 3.0
3.2 8.13
1001 454.05
0.258 0.38
0.310 0.46
0.048 0.07
85 85
95 95
More Options
2 AWG 2 AWG
3.0 3.0
3.9 9.91
1592 722.12
0.162 0.24
0.195 0.29
0.045 0.07
115 115
130 130
More Options
1 AWG 1 AWG
3.0 3.0
5.6 14.22
2008 910.81
0.128 0.19
0.154 0.23
0.046 0.07
130 130
145 145
More Options
1/0 AWG 1/0 AWG
3.0 3.0
5.9 14.99
2534 1149.40
0.102 0.15
0.122 0.18
0.044 0.07
150 150
170 170
More Options
2/0 AWG 2/0 AWG
3.0 3.0
6.4 16.26
3194 1448.77
0.081 0.12
0.097 0.14
0.043 0.06
175 175
195 195
More Options
3/0 AWG 3/0 AWG
3.0 3.0
6.9 17.53
4027 1826.61
0.064 0.10
0.078 0.12
0.042 0.06
200 200
225 225
More Options
4/0 AWG 4/0 AWG
3.0 3.0
7.4 18.80
5078 2303.34
0.051 0.08
0.062 0.09
0.041 0.06
230 230
260 260
More Options
250 KCMIL 250 KCMIL
3.0 3.0
8.3 21.08
6000 2721.55
0.043 0.06
0.053 0.08
0.041 0.06
255 255
290 290
More Options
350 KCMIL 350 KCMIL
3.0 3.0
9.7 24.64
8400 3810.17
0.031 0.05
0.039 0.06
0.040 0.06
310 310
350 350
More Options
500 KCMIL 500 KCMIL
3.0 3.0
13.0 33.02
12000 5443.10
0.022 0.03
0.029 0.04
0.039 0.06
380 380
430 430
More Options
600 KCMIL 600 KCMIL
3.0 3.0
14.3 36.32
14400 6531.72
0.018 0.03
0.025 0.04
0.039 0.06
420 420
475 475
More Options
750 KCMIL 750 KCMIL
3.0 3.0
15.6 39.62
18000 8164.66
0.014 0.02
0.022 0.03
0.038 0.06
475 475
535 535

* Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.

Standards & References

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test

Construction

  1. Conductor: Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Insulation: Polyvinyl Chloride (PVC) with nylon layer Type THHN/THWN
  3. Grounding Conductor: Class B compressed stranded bare copper per ASTM B3 and ASTM B8 (cable size 8 & 6 has insulated green ground)
  4. Filler: Paper filler (cable size 8 & 6 uses Polypropylene filler)
  5. Binder: Polyester flat thread binder tape for cable sizes larger than 2 AWG
  6. Overall Jacket: Polyvinyl Chloride (PVC) Jacket