Southwire’s 600 Volt power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. CT Rated 1/0 and Larger - Sunlight Resistant - For Direct Burial - Silicone Free
Conductor | Ground Wire | ||||||||
No. of Conductors | Size (AWG or kcmil) (mm2) | No. of Strands | Insulation Thickness (mils) (mm) | Size (AWG) | No. of Strands | Nom. OD (mils) (mm) | Nominal Total Weight (lbs/1000') (kgs/km) | Allowable Ampacity | |
576142 |
0
0
|
1/0 AWG
1/0 AWG
|
10
10
|
80
2.03
|
|
|
504
12.80
|
166
246
|
|
575991 |
1
1
|
4/0 AWG
4/0 AWG
|
19
19
|
80
2.03
|
|
|
643
16.33
|
293
436
|
|
576787 |
1
1
|
250 KCMIL
250 KCMIL
|
35
35
|
95
2.41
|
|
|
720
18.29
|
358
532
|
|
576137 |
1
1
|
350 KCMIL
350 KCMIL
|
35
35
|
95
2.41
|
|
|
816
20.73
|
472
702
|
|
567324 |
0
0
|
500 KCMIL
500 KCMIL
|
35
35
|
95
2.41
|
|
|
926
23.52
|
622
926
|
|
576219 |
1
1
|
750 KCMIL
750 KCMIL
|
58
58
|
110
2.79
|
|
|
1140
28.96
|
936
1394
|
|