SPEC45053 CU 600V XLPE Insulation Thermoplastic CPE-TP Jacket XHHW-2. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free

Type TC-ER Control Cable 600Volt Copper Cross Linked Polyethylene (XLPE) Insulation XHHW-2 Thermoplastic Chlorinated Polyethylene (CPE-TP) Jacket, Control Cable Conductor Identification Method 1 Table 2. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free

Download Category Specifications
PDF Excel Table

Application

Southwire’s 600 Volt Type TC-ER control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Sunlight Resistant - For Direct Burial - Silicone Free

Specifications

Select a set of products below for more information:
Cond. Size (AWG/Kcmil) Conductor Number Cond. Strands Diameter Over Conductor (in) (cm) Color Insulation Thickness (mils) (mm) Diameter Over Insulation (in) (cm) Ground (No. x AWG) Diameter Over Armor (in) (cm) Jacket Thickness (mils) (mm) Approx. OD (in) (cm) Copper Weight (lbs/1000') (kgs/km) Aluminum Weight (lbs/1000') (kgs/km) Approx. Weight (lbs/1000') (kgs/km) DC Resistance @ 25C (ohms/1000') (ohms/km) AC Resistance @ 75C (ohms/1000') (ohms/km) Min. Bend Radius (in) (cm) Raceway Ampacity @ 75C (amps) Raceway Ampacity @ 90C (amps)
890674
14 14
2.0 2.0
7 7
30 0.76
45 1.14
0.355 0.90
25 37
67 100
2.631 3.92
3.17 4.72
1.4 3.56
20 20
25 25
890675
14 14
3.0 3.0
7 7
30 0.76
45 1.14
0.376 0.96
38 57
91 135
2.631 3.92
3.17 4.72
1.5 3.81
20 20
25 25
890676
14 14
4.0 4.0
7 7
30 0.76
45 1.14
0.409 1.04
51 76
111 165
2.631 3.92
3.17 4.72
1.6 4.06
16 16
20 20
890677
14 14
5.0 5.0
7 7
30 0.76
45 1.14
0.447 1.14
64 95
129 192
2.631 3.92
3.17 4.72
1.8 4.57
16 16
20 20
890678
14 14
7.0 7.0
7 7
30 0.76
45 1.14
0.486 1.23
89 132
172 256
2.631 3.92
3.17 4.72
1.9 4.83
14 14
17 17
890679
14 14
9.0 9.0
7 7
30 0.76
60 1.52
0.592 1.50
114 170
232 345
2.631 3.92
3.17 4.72
2.4 6.10
14 14
17 17
550407
14 14
12.0 12.0
7 7
30 0.76
60 1.52
0.670 1.70
153 228
299 445
2.631 3.92
3.17 4.72
2.7 6.86
10 10
12 12
550411
12 12
2.0 2.0
7 7
30 0.76
45 1.14
0.388 0.99
40 60
89 132
1.662 2.47
2.002 2.98
1.6 4.06
25 25
30 30
890681
12 12
3.0 3.0
7 7
30 0.76
45 1.14
0.412 1.05
61 91
120 179
1.662 2.47
2.002 2.98
1.6 4.06
25 25
30 30
890682
12 12
4.0 4.0
7 7
30 0.76
45 1.14
0.449 1.14
81 121
154 229
1.662 2.47
2.002 2.98
1.8 4.57
20 20
24 24
890683
12 12
5.0 5.0
7 7
30 0.76
45 1.14
0.491 1.25
101 150
178 265
1.662 2.47
2.002 2.98
2.0 5.08
20 20
24 24
890684
12 12
12.0 12.0
7 7
30 0.76
60 1.52
0.738 1.87
244 363
408 607
1.662 2.47
2.002 2.98
3.0 7.62
12 12
15 15
890685
10 10
3.0 3.0
7 7
30 0.76
45 1.14
0.476 1.21
97 144
169 251
1.04 1.55
1.253 1.86
1.9 4.83
35 35
40 40
890686
10 10
4.0 4.0
7 7
30 0.76
45 1.14
0.547 1.39
129 192
228 339
1.04 1.55
1.253 1.86
2.2 5.59
28 28
32 32
550420
10 10
5.0 5.0
7 7
30 0.76
60 1.52
0.603 1.53
161 240
275 409
1.04 1.55
1.253 1.86
2.4 6.10
28 28
32 32
550421
10 10
7.0 7.0
7 7
30 0.76
60 1.52
0.657 1.67
226 336
364 542
1.04 1.55
1.253 1.86
2.6 6.60
24 24
28 28

Standards & References

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 2
  • ICEA S-73-532 Standard for Control, Thermocouple Extension and Instrumentation Cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test

Construction

  1. Conductor: 7 strands class B compressed copper per ASTM B3 and ASTM B8
  2. Insulation: Cross Linked Polyethylene (XLPE) XHHW-2, 30 Mils thick for all cable sizes
  3. Filler: Polypropylene filler on cables with 5 or less conductors
  4. Binder: Polyester flat thread binder tape applied for cables with more than 5 conductors
  5. Overall Jacket: Thermoplastic Chlorinated Polyethylene (CPE-TP) Jacket