Southwire’s 600 Volt Type TC-ER control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. 16 AWG wire is made in accordance with UL 66 Fixture Wire. Sunlight Resistant - For Direct Burial - Silicone Free
Cond. Size (AWG/Kcmil) | Conductor Number | Cond. Strands | Diameter Over Conductor (in) (cm) | Color | Insulation Thickness (mils) (mm) | Diameter Over Insulation (in) (cm) | Ground (No. x AWG) | Diameter Over Armor (in) (cm) | Jacket Thickness (mils) (mm) | Approx. OD (in) (cm) | Copper Weight (lbs/1000') (kgs/km) | Aluminum Weight (lbs/1000') (kgs/km) | Approx. Weight (lbs/1000') (kgs/km) | DC Resistance @ 25C (ohms/1000') (ohms/km) | AC Resistance @ 75C (ohms/1000') (ohms/km) | Min. Bend Radius (in) (cm) | Raceway Ampacity @ 75C (amps) | Raceway Ampacity @ 90C (amps) | |
561312 |
14
14
|
2.0
2.0
|
7
7
|
|
|
30
0.76
|
|
|
|
45
1.14
|
0.349
0.89
|
25
37
|
|
67
100
|
2.631
3.92
|
3.17
4.72
|
1.4
3.56
|
20
20
|
25
25
|
890159 |
14
14
|
3.0
3.0
|
7
7
|
|
|
30
0.76
|
|
|
|
45
1.14
|
0.373
0.95
|
38
57
|
|
93
138
|
2.631
3.92
|
3.17
4.72
|
1.5
3.81
|
20
20
|
25
25
|
561313 |
14
14
|
4.0
4.0
|
7
7
|
|
|
30
0.76
|
|
|
|
45
1.14
|
0.402
1.02
|
51
76
|
|
111
165
|
2.631
3.92
|
3.17
4.72
|
1.6
4.06
|
16
16
|
20
20
|
563383 |
14
14
|
5.0
5.0
|
7
7
|
|
|
30
0.76
|
|
|
|
45
1.14
|
0.443
1.13
|
64
95
|
|
135
201
|
2.631
3.92
|
3.17
4.72
|
1.8
4.57
|
16
16
|
20
20
|
597524 |
14
14
|
10.0
10.0
|
7
7
|
|
|
30
0.76
|
|
|
|
60
1.52
|
0.649
1.65
|
127
189
|
|
262
390
|
2.631
3.92
|
3.17
4.72
|
2.6
6.60
|
10
10
|
12
12
|
574615 |
12
12
|
2.0
2.0
|
7
7
|
|
|
30
0.76
|
|
|
|
45
1.14
|
0.384
0.98
|
40
60
|
|
89
132
|
1.662
2.47
|
2.002
2.98
|
1.5
3.81
|
25
25
|
30
30
|
890122 |
12
12
|
3.0
3.0
|
7
7
|
|
|
30
0.76
|
|
|
|
45
1.14
|
0.412
1.05
|
61
91
|
|
121
180
|
1.662
2.47
|
2.002
2.98
|
1.6
4.06
|
25
25
|
30
30
|
561319 |
12
12
|
4.0
4.0
|
7
7
|
|
|
30
0.76
|
|
|
|
45
1.14
|
0.445
1.13
|
81
121
|
|
152
226
|
1.662
2.47
|
2.002
2.98
|
1.8
4.57
|
20
20
|
24
24
|
574613 |
12
12
|
7.0
7.0
|
7
7
|
|
|
30
0.76
|
|
|
|
60
1.52
|
0.567
1.44
|
142
211
|
|
257
382
|
1.662
2.47
|
2.002
2.98
|
2.3
5.84
|
17
17
|
21
21
|
574614 |
12
12
|
12.0
12.0
|
7
7
|
|
|
30
0.76
|
|
|
|
60
1.52
|
0.732
1.86
|
244
363
|
|
411
612
|
1.662
2.47
|
2.002
2.98
|
2.9
7.37
|
12
12
|
15
15
|
577144 |
10
10
|
3.0
3.0
|
7
7
|
|
|
30
0.76
|
|
|
|
45
1.14
|
0.472
1.20
|
97
144
|
|
169
251
|
1.04
1.55
|
1.253
1.86
|
1.9
4.83
|
35
35
|
40
40
|
566720 |
10
10
|
4.0
4.0
|
7
7
|
|
|
30
0.76
|
|
|
|
45
1.14
|
0.547
1.39
|
129
192
|
|
235
350
|
1.04
1.55
|
1.253
1.86
|
2.2
5.59
|
28
28
|
32
32
|
574619 |
10
10
|
12.0
12.0
|
7
7
|
|
|
30
0.76
|
|
|
|
80
2.03
|
0.904
2.30
|
388
577
|
|
640
952
|
1.04
1.55
|
1.253
1.86
|
3.6
9.14
|
17
17
|
20
20
|