SPEC45054 CU 600V XLPE Insulation Thermoplastic LSZH-TP Jacket XHHW-2. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free

Type TC-ER Control Cable 600Volt Copper Conductors, Cross Linked Polyethylene (XLPE) Insulation XHHW-2 Thermoplastic SOLONON® Low Smoke Zero Halogen (LSZH-TP) Jacket, Control Cable Conductor Identification Method 1 Table 2. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free.

Download Category Specifications
PDF Excel Table

Application

Southwire’s 600 Volt Type TC-ER control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. 16 AWG wire is made in accordance with UL 66 Fixture Wire. Sunlight Resistant - For Direct Burial - Silicone Free

Specifications

Select a set of products below for more information:
Cond. Size (AWG/Kcmil) Conductor Number Cond. Strands Diameter Over Conductor (in) (cm) Color Insulation Thickness (mils) (mm) Diameter Over Insulation (in) (cm) Ground (No. x AWG) Diameter Over Armor (in) (cm) Jacket Thickness (mils) (mm) Approx. OD (in) (cm) Copper Weight (lbs/1000') (kgs/km) Aluminum Weight (lbs/1000') (kgs/km) Approx. Weight (lbs/1000') (kgs/km) DC Resistance @ 25C (ohms/1000') (ohms/km) AC Resistance @ 75C (ohms/1000') (ohms/km) Min. Bend Radius (in) (cm) Raceway Ampacity @ 75C (amps) Raceway Ampacity @ 90C (amps)
561312
14 14
2.0 2.0
7 7
30 0.76
45 1.14
0.349 0.89
25 37
67 100
2.631 3.92
3.17 4.72
1.4 3.56
20 20
25 25
890159
14 14
3.0 3.0
7 7
30 0.76
45 1.14
0.373 0.95
38 57
93 138
2.631 3.92
3.17 4.72
1.5 3.81
20 20
25 25
561313
14 14
4.0 4.0
7 7
30 0.76
45 1.14
0.402 1.02
51 76
111 165
2.631 3.92
3.17 4.72
1.6 4.06
16 16
20 20
563383
14 14
5.0 5.0
7 7
30 0.76
45 1.14
0.443 1.13
64 95
135 201
2.631 3.92
3.17 4.72
1.8 4.57
16 16
20 20
597524
14 14
10.0 10.0
7 7
30 0.76
60 1.52
0.649 1.65
127 189
262 390
2.631 3.92
3.17 4.72
2.6 6.60
10 10
12 12
574615
12 12
2.0 2.0
7 7
30 0.76
45 1.14
0.384 0.98
40 60
89 132
1.662 2.47
2.002 2.98
1.5 3.81
25 25
30 30
890122
12 12
3.0 3.0
7 7
30 0.76
45 1.14
0.412 1.05
61 91
121 180
1.662 2.47
2.002 2.98
1.6 4.06
25 25
30 30
561319
12 12
4.0 4.0
7 7
30 0.76
45 1.14
0.445 1.13
81 121
152 226
1.662 2.47
2.002 2.98
1.8 4.57
20 20
24 24
574613
12 12
7.0 7.0
7 7
30 0.76
60 1.52
0.567 1.44
142 211
257 382
1.662 2.47
2.002 2.98
2.3 5.84
17 17
21 21
574614
12 12
12.0 12.0
7 7
30 0.76
60 1.52
0.732 1.86
244 363
411 612
1.662 2.47
2.002 2.98
2.9 7.37
12 12
15 15
577144
10 10
3.0 3.0
7 7
30 0.76
45 1.14
0.472 1.20
97 144
169 251
1.04 1.55
1.253 1.86
1.9 4.83
35 35
40 40
566720
10 10
4.0 4.0
7 7
30 0.76
45 1.14
0.547 1.39
129 192
235 350
1.04 1.55
1.253 1.86
2.2 5.59
28 28
32 32
574619
10 10
12.0 12.0
7 7
30 0.76
80 2.03
0.904 2.30
388 577
640 952
1.04 1.55
1.253 1.86
3.6 9.14
17 17
20 20

Standards & References

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 66 Fixture Wire
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 2
  • ICEA S-73-532 Standard for Control, Thermocouple Extension and Instrumentation Cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test

Construction

  1. Conductor: 7 strands class B compressed bare copper per ASTM B3 and ASTM B8
  2. Insulation: Cross Linked Polyethylene (XLPE) Type XHHW-2 for cables 14 AWG or larger, 30 Mils thick for all cable sizes
  3. Filler: Polypropylene filler on cables with 5 or less conductors
  4. Binder: Polyester flat thread binder tape applied for cables with more than 5 conductors
  5. Overall Jacket: Thermoplastic SOLONON® Low Smoke Zero Halogen (LSZH-TP) Jacket