SPEC45102 CU 600V PVC-Nylon Insulation PVC Jacket THHN/THWN-2 With Green Ground. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free

Type TC-ER Control Cable 600Volt Copper Conductors, Polyvinyl Chloride (PVC) with nylon layer Insulation THHN/THWN Polyvinyl Chloride (PVC) Jacket with 1 Insulated Green CU Ground, Control Cable Conductor Identification Method 1 Table 2

Download Category Specifications
PDF Excel Table

Application

Southwire’s 600 Volt Type TC-ER control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 75°C in wet locations and 90°C in dry locations, 105°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10.

Specifications

Select a set of products below for more information:
Cond. Size (AWG/Kcmil) Conductor Number Cond. Strands Diameter Over Conductor (in) (cm) Color Insulation Thickness (mils) (mm) Diameter Over Insulation (in) (cm) Ground (No. x AWG) Diameter Over Armor (in) (cm) Jacket Thickness (mils) (mm) Approx. OD (in) (cm) Copper Weight (lbs/1000') (kgs/km) Aluminum Weight (lbs/1000') (kgs/km) Approx. Weight (lbs/1000') (kgs/km) DC Resistance @ 25C (ohms/1000') (ohms/km) AC Resistance @ 75C (ohms/1000') (ohms/km) Min. Bend Radius (in) (cm) Raceway Ampacity @ 75C (amps) Raceway Ampacity @ 90C (amps)
606806
14 14
3.0 3.0
7 7
15 0.38
45 1.14
0.349 0.89
51 76
90 134
2.631 3.92
3.17 4.72
1.4 3.56
20 20
25 25
606814
14 14
4.0 4.0
7 7
15 0.38
45 1.14
0.384 0.98
64 95
111 165
2.631 3.92
3.17 4.72
1.5 3.81
16 16
20 20
606723
12 12
3.0 3.0
7 7
15 0.38
45 1.14
0.364 0.92
81 121
131 195
1.662 2.47
2.002 2.98
1.5 3.81
25 25
30 30
606723
12 12
3.0 3.0
7 7
15 0.38
45 1.14
0.364 0.92
81 121
131 195
1.662 2.47
2.002 2.98
1.5 3.81
25 25
30 30
606798
12 12
4.0 4.0
7 7
15 0.38
45 1.14
0.406 1.03
101 150
157 234
1.662 2.47
2.002 2.98
1.6 4.06
20 20
24 24
605543
10 10
3.0 3.0
7 7
20 0.51
45 1.14
0.488 1.24
129 192
204 304
1.04 1.55
1.253 1.86
2.0 5.08
35 35
40 40
606863
10 10
4.0 4.0
7 7
20 0.51
45 1.14
0.565 1.44
161 240
259 385
1.04 1.55
1.253 1.86
2.3 5.84
28 28
32 32
644497
8 8
3.0 3.0
7 7
30 0.76
60 1.52
0.647 1.64
186 277
310 461
0.653 0.97
0.786 1.17
2.6 6.60
50 50
55 55

Standards & References

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 2
  • ICEA S-73-532 Standard for Control, Thermocouple Extension and Instrumentation Cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy

Construction

  1. Conductor: 7 strands class B compressed bare copper per ASTM B3 and ASTM B8
  2. Insulation: Polyvinyl Chloride (PVC) with nylon layer THHN/THWN
  3. Grounding Conductor: Class B compressed stranded copper with green insulation
  4. Filler: Polypropylene filler
  5. Overall Jacket: Polyvinyl Chloride (PVC) Jacket