Southwire’s 600 or 1000 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Sunlight Resistant - For Direct Burial - Silicone Free
Cond. Size (AWG/Kcmil) | Conductor Number | Cond. Strands | Diameter Over Conductor (in) (cm) | Insulation Thickness (mils) (mm) | Diameter Over Insulation (in) (cm) | Ground (No. x AWG) | Drain Wire | Diameter Over Shield (in) (cm) | Inner Jacket Thickness (mils) (mm) | Diameter Over Armor (in) (cm) | Jacket Thickness (mils) (mm) | Approx. OD (in) (cm) | Copper Weight (lbs/1000') (kgs/km) | Aluminum Weight (lbs/1000') (kgs/km) | Approx. Weight (lbs/1000') (kgs/km) | |
480590 |
8
8
|
3.0
3.0
|
7
7
|
0.141
0.36
|
45
1.14
|
|
10 GG
10 GG
|
|
|
|
|
60
1.52
|
0.688
1.75
|
186
277
|
|
327
487
|
480608 |
6
6
|
3.0
3.0
|
7
7
|
0.177
0.45
|
45
1.14
|
|
8 GG
8 GG
|
|
|
|
|
60
1.52
|
0.782
1.99
|
297
442
|
|
466
693
|
480616 |
4
4
|
3.0
3.0
|
7
7
|
0.225
0.57
|
45
1.14
|
|
8
8
|
|
|
|
|
60
1.52
|
0.806
2.05
|
441
656
|
|
612
911
|
480624 |
2
2
|
3.0
3.0
|
7
7
|
0.282
0.72
|
45
1.14
|
|
6
6
|
|
|
|
|
80
2.03
|
0.982
2.49
|
702
1045
|
|
927
1380
|
480632 |
1
1
|
3.0
3.0
|
19
19
|
0.322
0.82
|
55
1.40
|
|
6
6
|
|
|
|
|
80
2.03
|
1.106
2.81
|
864
1286
|
|
1142
1699
|
480640 |
1/0
1/0
|
3.0
3.0
|
19
19
|
0.361
0.92
|
55
1.40
|
|
6
6
|
|
|
|
|
80
2.03
|
1.200
3.05
|
1069
1591
|
|
1417
2109
|
480657 |
2/0
2/0
|
3.0
3.0
|
19
19
|
0.405
1.03
|
55
1.40
|
|
6
6
|
|
|
|
|
80
2.03
|
1.295
3.29
|
1326
1973
|
|
1723
2564
|
480665 |
3/0
3/0
|
3.0
3.0
|
19
19
|
0.456
1.16
|
55
1.40
|
|
4
4
|
|
|
|
|
80
2.03
|
1.399
3.55
|
1699
2528
|
|
2065
3073
|
480673 |
4/0
4/0
|
3.0
3.0
|
19
19
|
0.512
1.30
|
55
1.40
|
|
4
4
|
|
|
|
|
80
2.03
|
1.494
3.79
|
2109
3139
|
|
2502
3723
|
480681 |
250
250
|
3.0
3.0
|
37
37
|
0.558
1.42
|
65
1.65
|
|
4
4
|
|
|
|
|
80
2.03
|
1.619
4.11
|
2469
3674
|
|
2940
4375
|
480707 |
350
350
|
3.0
3.0
|
37
37
|
0.661
1.68
|
65
1.65
|
|
3
3
|
|
|
|
|
115
2.92
|
1.910
4.85
|
3438
5116
|
|
4127
6142
|
480715 |
400
400
|
3.0
3.0
|
37
37
|
0.705
1.79
|
65
1.65
|
|
3
3
|
|
|
|
|
115
2.92
|
2.014
5.12
|
3906
5813
|
|
4756
7078
|
480723 |
500
500
|
3.0
3.0
|
37
37
|
0.789
2.00
|
65
1.65
|
|
2
2
|
|
|
|
|
115
2.92
|
2.167
5.50
|
4884
7268
|
|
5701
8484
|
593173 |
600
600
|
3.0
3.0
|
61
61
|
0.865
2.20
|
80
2.03
|
|
3/0
3/0
|
|
|
|
|
115
2.92
|
2.417
6.14
|
6136
9131
|
|
7286
10843
|
554410 |
750
750
|
3.0
3.0
|
61
61
|
0.968
2.46
|
80
2.03
|
|
1
1
|
|
|
|
|
115
2.92
|
2.631
6.68
|
7277
10829
|
|
8597
12794
|
Cond. Size (AWG/Kcmil) | Conductor Number | Min. Bend Radius (in) (cm) | Max Pull Tension (lbs) (kg) | DC Resistance @ 25C (ohms/1000') (ohms/km) | AC Resistance @ 75C (ohms/1000') (ohms/km) | Capacitive Reactance (Mohms x 1000ft) (Mohms x km) | Inductive Reactance (ohms/1000') (ohms/km) | Shield Short Circuit Current 6 Cycles (amps) | Raceway Ampacity @ 75C (amps) | Raceway Ampacity @ 90C (amps) | |
480590 |
8
8
|
3.0
3.0
|
2.8
7.11
|
396
179.62
|
0.653
0.97
|
0.786
1.17
|
|
0.052
0.08
|
|
50
50
|
55
55
|
480608 |
6
6
|
3.0
3.0
|
3.1
7.87
|
629
285.31
|
0.411
0.61
|
0.495
0.74
|
|
0.051
0.08
|
|
65
65
|
75
75
|
480616 |
4
4
|
3.0
3.0
|
3.2
8.13
|
1001
454.05
|
0.258
0.38
|
0.31
0.46
|
|
0.048
0.07
|
|
85
85
|
95
95
|
480624 |
2
2
|
3.0
3.0
|
3.9
9.91
|
1592
722.12
|
0.162
0.24
|
0.195
0.29
|
|
0.045
0.07
|
|
115
115
|
130
130
|
480632 |
1
1
|
3.0
3.0
|
5.5
13.97
|
2008
910.81
|
0.128
0.19
|
0.154
0.23
|
|
0.046
0.07
|
|
130
130
|
145
145
|
480640 |
1/0
1/0
|
3.0
3.0
|
6.0
15.24
|
2534
1149.40
|
0.102
0.15
|
0.122
0.18
|
|
0.044
0.07
|
|
150
150
|
170
170
|
480657 |
2/0
2/0
|
3.0
3.0
|
6.5
16.51
|
3194
1448.77
|
0.081
0.12
|
0.097
0.14
|
|
0.043
0.06
|
|
175
175
|
195
195
|
480665 |
3/0
3/0
|
3.0
3.0
|
7.0
17.78
|
4027
1826.61
|
0.064
0.10
|
0.078
0.12
|
|
0.042
0.06
|
|
200
200
|
225
225
|
480673 |
4/0
4/0
|
3.0
3.0
|
7.5
19.05
|
5078
2303.34
|
0.051
0.08
|
0.062
0.09
|
|
0.041
0.06
|
|
230
230
|
260
260
|
480681 |
250
250
|
3.0
3.0
|
8.1
20.57
|
6000
2721.55
|
0.043
0.06
|
0.053
0.08
|
|
0.041
0.06
|
|
255
255
|
290
290
|
480707 |
350
350
|
3.0
3.0
|
9.6
24.38
|
8400
3810.17
|
0.031
0.05
|
0.039
0.06
|
|
0.04
0.06
|
|
310
310
|
350
350
|
480715 |
400
400
|
3.0
3.0
|
12.1
30.73
|
9600
4354.48
|
0.027
0.04
|
0.035
0.05
|
|
0.04
0.06
|
|
335
335
|
380
380
|
480723 |
500
500
|
3.0
3.0
|
13.0
33.02
|
12000
5443.10
|
0.022
0.03
|
0.029
0.04
|
|
0.039
0.06
|
|
380
380
|
430
430
|
593173 |
600
600
|
3.0
3.0
|
14.5
36.83
|
14400
6531.72
|
0.018
0.03
|
0.025
0.04
|
|
0.039
0.06
|
|
420
420
|
475
475
|
554410 |
750
750
|
3.0
3.0
|
15.8
40.13
|
18000
8164.66
|
0.014
0.02
|
0.022
0.03
|
|
0.038
0.06
|
|
475
475
|
535
535
|