Southwire’s 600 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. VW-1 rated
Cond. Size (AWG/Kcmil) | Conductor Number | Cond. Strands | Diameter Over Conductor (in) (cm) | Insulation Thickness (mils) (mm) | Diameter Over Insulation (in) (cm) | Ground (No. x AWG) | Drain Wire | Diameter Over Shield (in) (cm) | Inner Jacket Thickness (mils) (mm) | Diameter Over Armor (in) (cm) | Jacket Thickness (mils) (mm) | Approx. OD (in) (cm) | Copper Weight (lbs/1000') (kgs/km) | Aluminum Weight (lbs/1000') (kgs/km) | Approx. Weight (lbs/1000') (kgs/km) | |
591982 |
8
8
|
4.0
4.0
|
7
7
|
0.141
0.36
|
45
1.14
|
|
|
|
|
|
|
60
1.52
|
0.724
1.84
|
238
354
|
|
385
573
|
591984 |
6
6
|
4.0
4.0
|
7
7
|
0.177
0.45
|
45
1.14
|
|
|
|
|
|
|
60
1.52
|
0.816
2.07
|
378
563
|
|
553
823
|
591986 |
4
4
|
4.0
4.0
|
7
7
|
0.225
0.57
|
45
1.14
|
|
|
|
|
|
|
80
2.03
|
0.936
2.38
|
572
851
|
|
802
1194
|
591988 |
2
2
|
4.0
4.0
|
7
7
|
0.282
0.72
|
45
1.14
|
|
|
|
|
|
|
80
2.03
|
1.123
2.85
|
909
1353
|
|
1214
1807
|
591990 |
1
1
|
4.0
4.0
|
19
19
|
0.322
0.82
|
55
1.40
|
|
|
|
|
|
|
80
2.03
|
1.279
3.25
|
1125
1674
|
|
1527
2272
|
591992 |
1/0
1/0
|
4.0
4.0
|
19
19
|
0.361
0.92
|
55
1.40
|
|
|
|
|
|
|
80
2.03
|
1.357
3.45
|
1399
2082
|
|
1828
2720
|
591994 |
2/0
2/0
|
4.0
4.0
|
19
19
|
0.405
1.03
|
55
1.40
|
|
|
|
|
|
|
80
2.03
|
1.464
3.72
|
1742
2592
|
|
2210
3289
|
591997 |
4/0
4/0
|
4.0
4.0
|
19
19
|
0.512
1.30
|
55
1.40
|
|
|
|
|
|
|
110
2.79
|
1.740
4.42
|
2769
4121
|
|
3369
5014
|
591999 |
250
250
|
4.0
4.0
|
37
37
|
0.558
1.42
|
65
1.65
|
|
|
|
|
|
|
110
2.79
|
1.939
4.93
|
3248
4834
|
|
4006
5962
|
592001 |
350
350
|
4.0
4.0
|
37
37
|
0.661
1.68
|
65
1.65
|
|
|
|
|
|
|
110
2.79
|
2.202
5.59
|
4530
6741
|
|
5420
8066
|
592003 |
500
500
|
4.0
4.0
|
37
37
|
0.789
2.00
|
65
1.65
|
|
|
|
|
|
|
110
2.79
|
2.464
6.26
|
6443
9588
|
|
7386
10992
|
646849 |
600
600
|
4.0
4.0
|
61
61
|
0.865
2.20
|
80
2.03
|
|
|
|
|
|
|
140
3.56
|
2.790
7.09
|
7691
11445
|
|
9439
14047
|
Cond. Size (AWG/Kcmil) | Conductor Number | Min. Bend Radius (in) (cm) | Max Pull Tension (lbs) (kg) | DC Resistance @ 25C (ohms/1000') (ohms/km) | AC Resistance @ 75C (ohms/1000') (ohms/km) | Capacitive Reactance (Mohms x 1000ft) (Mohms x km) | Inductive Reactance (ohms/1000') (ohms/km) | Shield Short Circuit Current 6 Cycles (amps) | Raceway Ampacity @ 75C (amps) | Raceway Ampacity @ 90C (amps) | |
591982 |
8
8
|
4.0
4.0
|
2.9
7.37
|
422
191.42
|
0.653
0.97
|
0.786
1.17
|
|
0.052
0.08
|
|
40
40
|
44
44
|
591984 |
6
6
|
4.0
4.0
|
3.3
8.38
|
671
304.36
|
0.411
0.61
|
0.495
0.74
|
|
0.051
0.08
|
|
52
52
|
60
60
|
591986 |
4
4
|
4.0
4.0
|
3.7
9.40
|
1068
484.44
|
0.258
0.38
|
0.31
0.46
|
|
0.048
0.07
|
|
68
68
|
76
76
|
591988 |
2
2
|
4.0
4.0
|
5.6
14.22
|
1698
770.20
|
0.162
0.24
|
0.195
0.29
|
|
0.045
0.07
|
|
92
92
|
104
104
|
591990 |
1
1
|
4.0
4.0
|
6.4
16.26
|
2142
971.59
|
0.128
0.19
|
0.154
0.23
|
|
0.046
0.07
|
|
104
104
|
116
116
|
591992 |
1/0
1/0
|
4.0
4.0
|
6.8
17.27
|
2703
1226.06
|
0.102
0.15
|
0.122
0.18
|
|
0.044
0.07
|
|
120
120
|
136
136
|
591994 |
2/0
2/0
|
4.0
4.0
|
7.3
18.54
|
3407
1545.39
|
0.081
0.12
|
0.097
0.14
|
|
0.043
0.06
|
|
140
140
|
156
156
|
591997 |
4/0
4/0
|
4.0
4.0
|
8.7
22.10
|
5416
2456.65
|
0.051
0.08
|
0.062
0.09
|
|
0.041
0.06
|
|
184
184
|
208
208
|
591999 |
250
250
|
4.0
4.0
|
9.7
24.64
|
6400
2902.99
|
0.043
0.06
|
0.053
0.08
|
|
0.041
0.06
|
|
204
204
|
232
232
|
592001 |
350
350
|
4.0
4.0
|
13.2
33.53
|
8960
4064.18
|
0.031
0.05
|
0.039
0.06
|
|
0.04
0.06
|
|
248
248
|
280
280
|
592003 |
500
500
|
4.0
4.0
|
14.8
37.59
|
12800
5805.98
|
0.022
0.03
|
0.029
0.04
|
|
0.039
0.06
|
|
304
304
|
344
344
|
646849 |
600
600
|
4.0
4.0
|
16.7
42.42
|
15360
6967.17
|
0.018
0.03
|
0.025
0.04
|
|
0.039
0.06
|
|
336
336
|
380
380
|