SPEC45262 TCU 600/1000V EPR Insulation Thermoplastic CPE-TP Jacket XHHW-2. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free

Type TC-ER Power Cable 600Volt Four Conductor Copper, Ethylene Propylene Rubber (EPR) insulation XHHW-2 Thermoplastic Chlorinated Polyethylene (CPE-TP) Jacket with 1 Tinned CU Ground. VW-1 rated

Download Category Specifications
PDF Excel Table

Application

Southwire’s 600 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. VW-1 rated

Specifications

Select a set of products below for more information:
Cond. Size (AWG/Kcmil) Conductor Number Cond. Strands Diameter Over Conductor (in) (cm) Insulation Thickness (mils) (mm) Diameter Over Insulation (in) (cm) Ground (No. x AWG) Drain Wire Diameter Over Shield (in) (cm) Inner Jacket Thickness (mils) (mm) Diameter Over Armor (in) (cm) Jacket Thickness (mils) (mm) Approx. OD (in) (cm) Copper Weight (lbs/1000') (kgs/km) Aluminum Weight (lbs/1000') (kgs/km) Approx. Weight (lbs/1000') (kgs/km)
591982
8 8
4.0 4.0
7 7
0.141 0.36
45 1.14
60 1.52
0.724 1.84
238 354
385 573
591984
6 6
4.0 4.0
7 7
0.177 0.45
45 1.14
60 1.52
0.816 2.07
378 563
553 823
591986
4 4
4.0 4.0
7 7
0.225 0.57
45 1.14
80 2.03
0.936 2.38
572 851
802 1194
591988
2 2
4.0 4.0
7 7
0.282 0.72
45 1.14
80 2.03
1.123 2.85
909 1353
1214 1807
591990
1 1
4.0 4.0
19 19
0.322 0.82
55 1.40
80 2.03
1.279 3.25
1125 1674
1527 2272
591992
1/0 1/0
4.0 4.0
19 19
0.361 0.92
55 1.40
80 2.03
1.357 3.45
1399 2082
1828 2720
591994
2/0 2/0
4.0 4.0
19 19
0.405 1.03
55 1.40
80 2.03
1.464 3.72
1742 2592
2210 3289
591997
4/0 4/0
4.0 4.0
19 19
0.512 1.30
55 1.40
110 2.79
1.740 4.42
2769 4121
3369 5014
591999
250 250
4.0 4.0
37 37
0.558 1.42
65 1.65
110 2.79
1.939 4.93
3248 4834
4006 5962
592001
350 350
4.0 4.0
37 37
0.661 1.68
65 1.65
110 2.79
2.202 5.59
4530 6741
5420 8066
592003
500 500
4.0 4.0
37 37
0.789 2.00
65 1.65
110 2.79
2.464 6.26
6443 9588
7386 10992
646849
600 600
4.0 4.0
61 61
0.865 2.20
80 2.03
140 3.56
2.790 7.09
7691 11445
9439 14047
Cond. Size (AWG/Kcmil) Conductor Number Min. Bend Radius (in) (cm) Max Pull Tension (lbs) (kg) DC Resistance @ 25C (ohms/1000') (ohms/km) AC Resistance @ 75C (ohms/1000') (ohms/km) Capacitive Reactance (Mohms x 1000ft) (Mohms x km) Inductive Reactance (ohms/1000') (ohms/km) Shield Short Circuit Current 6 Cycles (amps) Raceway Ampacity @ 75C (amps) Raceway Ampacity @ 90C (amps)
591982
8 8
4.0 4.0
2.9 7.37
422 191.42
0.653 0.97
0.786 1.17
0.052 0.08
40 40
44 44
591984
6 6
4.0 4.0
3.3 8.38
671 304.36
0.411 0.61
0.495 0.74
0.051 0.08
52 52
60 60
591986
4 4
4.0 4.0
3.7 9.40
1068 484.44
0.258 0.38
0.31 0.46
0.048 0.07
68 68
76 76
591988
2 2
4.0 4.0
5.6 14.22
1698 770.20
0.162 0.24
0.195 0.29
0.045 0.07
92 92
104 104
591990
1 1
4.0 4.0
6.4 16.26
2142 971.59
0.128 0.19
0.154 0.23
0.046 0.07
104 104
116 116
591992
1/0 1/0
4.0 4.0
6.8 17.27
2703 1226.06
0.102 0.15
0.122 0.18
0.044 0.07
120 120
136 136
591994
2/0 2/0
4.0 4.0
7.3 18.54
3407 1545.39
0.081 0.12
0.097 0.14
0.043 0.06
140 140
156 156
591997
4/0 4/0
4.0 4.0
8.7 22.10
5416 2456.65
0.051 0.08
0.062 0.09
0.041 0.06
184 184
208 208
591999
250 250
4.0 4.0
9.7 24.64
6400 2902.99
0.043 0.06
0.053 0.08
0.041 0.06
204 204
232 232
592001
350 350
4.0 4.0
13.2 33.53
8960 4064.18
0.031 0.05
0.039 0.06
0.04 0.06
248 248
280 280
592003
500 500
4.0 4.0
14.8 37.59
12800 5805.98
0.022 0.03
0.029 0.04
0.039 0.06
304 304
344 344
646849
600 600
4.0 4.0
16.7 42.42
15360 6967.17
0.018 0.03
0.025 0.04
0.039 0.06
336 336
380 380

Standards & References

  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 44 VW-1 Vertical flame test on individual conductors
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test

Construction

  1. Conductor: Class B compressed stranded tinned copper per ASTM B33 and ASTM B8
  2. Insulation: Ethylene Propylene Rubber (EPR) Type XHHW-2
  3. Grounding Conductor: Class B compressed stranded tinned copper per ASTM B33 and ASTM B8
  4. Filler: Paper filler (cable size 8 & 6 uses Polypropylene filler)
  5. Binder: Polyester flat thread binder tape for cable sizes larger than 2 AWG
  6. Overall Jacket: Thermoplastic Chlorinated Polyethylene (CPE-TP) Jacket

Resources