Southwire’s 600 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. VW-1 rated
Conductor | Ground Wire | ||||||||
No. of Conductors | Size (AWG or kcmil) (mm2) | No. of Strands | Insulation Thickness (mils) (mm) | Size (AWG) | No. of Strands | Nom. OD (mils) (mm) | Nominal Total Weight (lbs/1000') (kgs/km) | Allowable Ampacity | |
591982 |
4
4
|
8 AWG
8 AWG
|
7
7
|
45
1.14
|
10
10
|
|
724
18.39
|
386
574
|
|
591984 |
4
4
|
6 AWG
6 AWG
|
7
7
|
45
1.14
|
8
8
|
|
816
20.73
|
553
823
|
|
591986 |
4
4
|
4 AWG
4 AWG
|
7
7
|
45
1.14
|
8
8
|
|
936
23.77
|
803
1195
|
|
591988 |
4
4
|
2 AWG
2 AWG
|
7
7
|
45
1.14
|
6
6
|
|
1123
28.52
|
1214
1807
|
|
591990 |
4
4
|
1 AWG
1 AWG
|
19
19
|
55
1.40
|
6
6
|
|
1279
32.49
|
1532
2280
|
|
591992 |
4
4
|
1/0 AWG
1/0 AWG
|
19
19
|
55
1.40
|
6
6
|
|
1357
34.47
|
1828
2721
|
|
591994 |
4
4
|
2/0 AWG
2/0 AWG
|
19
19
|
55
1.40
|
6
6
|
|
1464
37.19
|
2216
3297
|
|
591997 |
4
4
|
4/0 AWG
4/0 AWG
|
19
19
|
55
1.40
|
4
4
|
|
1740
44.20
|
3376
5025
|
|
591999 |
4
4
|
250 KCMIL
250 KCMIL
|
37
37
|
65
1.65
|
4
4
|
|
1939
49.25
|
4016
5976
|
|
592001 |
4
4
|
350 KCMIL
350 KCMIL
|
37
37
|
65
1.65
|
3
3
|
|
2202
55.93
|
5421
8067
|
|
592003 |
4
4
|
500 KCMIL
500 KCMIL
|
37
37
|
65
1.65
|
2
2
|
|
2464
62.59
|
7386
10992
|
|
646849 |
4
4
|
600 KCMIL
600 KCMIL
|
61
61
|
80
2.03
|
2
2
|
|
2790
70.88
|
9440
14048
|
|