Applications and Features: Power supply cable for VFDs and motors, suitable for cable tray, conduit, raceways, exposed run (TC-ER) and conforming to NFPA 79 2018. Suitable for free air and direct burial. Its flexible design is ideal for use on operation processes in accordance with NEC® Articles 336, 501 and 502 including, but not limited to: fans, pumps, conveyors, compressors, elevators and lifts, extruders, crushers and presses, assembly lines, food and beverage, wind energy and data centers. Cable is rated for -40C Cold Bend and Impact. Multiple approvals for multiple applications.
Cond. Size (AWG/Kcmil) | Conductor Number | Cond. Strands | Diameter Over Conductor (in) (cm) | Insulation Thickness (mils) (mm) | Diameter Over Insulation (in) (cm) | Ground (No. x AWG) | Drain Wire | Diameter Over Shield (in) (cm) | Inner Jacket Thickness (mils) (mm) | Diameter Over Armor (in) (cm) | Jacket Thickness (mils) (mm) | Approx. OD (in) (cm) | Copper Weight (lbs/1000') (kgs/km) | Aluminum Weight (lbs/1000') (kgs/km) | Approx. Weight (lbs/1000') (kgs/km) | |
645824 |
16
16
|
3.0
3.0
|
26
26
|
0.059
0.15
|
30
0.76
|
|
|
1x16
1x16
|
0.314
0.80
|
|
|
47
1.19
|
0.408
1.04
|
58
86
|
|
112
167
|
645825 |
14
14
|
3.0
3.0
|
41
41
|
0.073
0.19
|
30
0.76
|
|
|
1x14
1x14
|
0.350
0.89
|
|
|
47
1.19
|
0.444
1.13
|
84
125
|
|
145
216
|
645826 |
12
12
|
3.0
3.0
|
65
65
|
0.094
0.24
|
30
0.76
|
|
|
1x12
1x12
|
0.396
1.01
|
|
|
47
1.19
|
0.490
1.24
|
124
185
|
|
195
290
|
645827 |
10
10
|
3.0
3.0
|
105
105
|
0.117
0.30
|
30
0.76
|
|
|
1x10
1x10
|
0.467
1.19
|
|
|
62
1.57
|
0.591
1.50
|
189
281
|
|
291
433
|
677299 |
8
8
|
3.0
3.0
|
168
168
|
0.153
0.39
|
45
1.14
|
|
|
4x14
4x14
|
0.650
1.65
|
|
|
62
1.57
|
0.774
1.97
|
302
449
|
|
480
714
|
Cond. Size (AWG/Kcmil) | Conductor Number | Min. Bend Radius (in) (cm) | Max Pull Tension (lbs) (kg) | DC Resistance @ 25C (ohms/1000') (ohms/km) | AC Resistance @ 75C (ohms/1000') (ohms/km) | Capacitive Reactance (Mohms x 1000ft) (Mohms x km) | Inductive Reactance (ohms/1000') (ohms/km) | Shield Short Circuit Current 6 Cycles (amps) | Raceway Ampacity @ 75C (amps) | Raceway Ampacity @ 90C (amps) | |
645824 |
16
16
|
3.0
3.0
|
4.9
12.45
|
61
27.67
|
4.487
6.68
|
5.406
8.05
|
0.051
0.08
|
0.033
0.05
|
|
-
-
|
18
18
|
645825 |
14
14
|
3.0
3.0
|
5.3
13.46
|
98
44.45
|
2.814
4.19
|
3.391
5.05
|
0.043
0.06
|
0.058
0.09
|
|
20
20
|
25
25
|
645826 |
12
12
|
3.0
3.0
|
5.9
14.99
|
156
70.76
|
1.774
2.64
|
2.137
3.18
|
0.036
0.05
|
0.054
0.08
|
|
25
25
|
30
30
|
645827 |
10
10
|
3.0
3.0
|
7.1
18.03
|
249
112.94
|
1.111
1.65
|
1.339
1.99
|
0.03
0.04
|
0.05
0.07
|
|
35
35
|
40
40
|
677299 |
8
8
|
3.0
3.0
|
9.3
23.62
|
396
179.62
|
0.715
1.06
|
0.861
1.28
|
0.033
0.05
|
0.052
0.08
|
|
50
50
|
55
55
|