SPEC45006 CU 600V EPR Insulation Thermoset LSZH-TS Jacket RHH/RHW-2. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free

Power Cable 600Volt Single Conductor Copper, Ethylene Propylene Rubber (EPR) insulation RHH/RHW-2 USE-2 Thermoset SOLONON® Low Smoke Zero Halogen (LSZH-TS) Jacket. CT Rated 1/0 and Larger - Silicone Free

Download Category Specifications
PDF Excel Table

Application

Southwire’s 600 Volt power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. CT Rated 1/0 and Larger - Silicone Free

Specifications

Select a set of products below for more information:
Cond. Size (AWG/Kcmil) Conductor Number Cond. Strands Diameter Over Conductor (in) (cm) Insulation Thickness (mils) (mm) Diameter Over Insulation (in) (cm) Ground (No. x AWG) Drain Wire Diameter Over Shield (in) (cm) Inner Jacket Thickness (mils) (mm) Diameter Over Armor (in) (cm) Jacket Thickness (mils) (mm) Approx. OD (in) (cm) Copper Weight (lbs/1000') (kgs/km) Aluminum Weight (lbs/1000') (kgs/km) Approx. Weight (lbs/1000') (kgs/km)
890660
8 8
0.0 0.0
7 7
0.141 0.36
45 1.14
15 0.38
0.268 0.68
50 74
74 110
890659
6 6
1.0 1.0
7 7
0.177 0.45
45 1.14
30 0.76
0.338 0.86
81 121
119 177
551088
2 2
1.0 1.0
7 7
0.282 0.72
45 1.14
30 0.76
0.438 1.11
204 304
258 384
561561
1/0 1/0
1.0 1.0
19 19
0.361 0.92
55 1.40
45 1.14
0.575 1.46
326 485
418 622
561560
2/0 2/0
1.0 1.0
19 19
0.405 1.03
55 1.40
45 1.14
0.617 1.57
410 610
511 760
581799
3/0 3/0
1.0 1.0
19 19
0.456 1.16
55 1.40
45 1.14
0.669 1.70
518 771
628 935
561556
4/0 4/0
1.0 1.0
19 19
0.512 1.30
55 1.40
45 1.14
0.711 1.81
653 972
770 1146
561553
350 350
1.0 1.0
37 37
0.661 1.68
65 1.65
65 1.65
0.916 2.33
1080 1607
1280 1905
890658
500 500
1.0 1.0
37 37
0.789 2.00
65 1.65
65 1.65
1.041 2.64
1543 2296
1775 2641
551091
750 750
1.0 1.0
61 61
0.968 2.46
80 2.03
65 1.65
1.246 3.16
2315 3445
2625 3906
Cond. Size (AWG/Kcmil) Conductor Number Min. Bend Radius (in) (cm) Max Pull Tension (lbs) (kg) DC Resistance @ 25C (ohms/1000') (ohms/km) AC Resistance @ 75C (ohms/1000') (ohms/km) Capacitive Reactance (Mohms x 1000ft) (Mohms x km) Inductive Reactance (ohms/1000') (ohms/km) Shield Short Circuit Current 6 Cycles (amps) Raceway Ampacity @ 75C (amps) Raceway Ampacity @ 90C (amps)
890660
8 8
0.0 0.0
1.0 2.54
132 59.87
0.653 0.97
0.786 1.17
0.052 0.08
50 50
55 55
890659
6 6
1.0 1.0
1.3 3.30
209 94.80
0.411 0.61
0.495 0.74
0.051 0.08
65 65
75 75
551088
2 2
1.0 1.0
1.7 4.32
530 240.40
0.162 0.24
0.195 0.29
0.045 0.07
115 115
130 130
561561
1/0 1/0
1.0 1.0
2.3 5.84
844 382.83
0.102 0.15
0.122 0.18
0.044 0.07
150 150
170 170
561560
2/0 2/0
1.0 1.0
2.4 6.10
1064 482.62
0.081 0.12
0.097 0.14
0.043 0.06
175 175
195 195
581799
3/0 3/0
1.0 1.0
2.6 6.60
1342 608.72
0.064 0.10
0.078 0.12
0.042 0.06
200 200
225 225
561556
4/0 4/0
1.0 1.0
2.8 7.11
1692 767.48
0.051 0.08
0.062 0.09
0.041 0.06
230 230
260 260
561553
350 350
1.0 1.0
3.6 9.14
2800 1270.06
0.031 0.05
0.039 0.06
0.04 0.06
310 310
350 350
890658
500 500
1.0 1.0
5.2 13.21
4000 1814.37
0.022 0.03
0.029 0.04
0.039 0.06
380 380
430 430
551091
750 750
1.0 1.0
6.2 15.75
6000 2721.55
0.014 0.02
0.022 0.03
0.038 0.06
475 475
535 535

Standards & References

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • CT USE Sizes 1/0 AWG and Larger

Construction

  1. Conductor: Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Binder Tape: Mylar Tape
  3. Insulation: Ethylene Propylene Rubber (EPR) Type RHH/RHW-2 USE-2
  4. Overall Jacket: Thermoset SOLONON® Low Smoke Zero Halogen (LSZH-TS) Silicone-Free Jacket