Southwire’s 600 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Sunlight Resistant - For Direct Burial - Silicone Free
Cond. Size (AWG/Kcmil) | Conductor Number | Cond. Strands | Diameter Over Conductor (in) (cm) | Insulation Thickness (mils) (mm) | Diameter Over Insulation (in) (cm) | Ground (No. x AWG) | Drain Wire | Diameter Over Shield (in) (cm) | Inner Jacket Thickness (mils) (mm) | Diameter Over Armor (in) (cm) | Jacket Thickness (mils) (mm) | Approx. OD (in) (cm) | Copper Weight (lbs/1000') (kgs/km) | Aluminum Weight (lbs/1000') (kgs/km) | Approx. Weight (lbs/1000') (kgs/km) | |
890670 |
8
8
|
3.0
3.0
|
7
7
|
0.141
0.36
|
45
1.14
|
|
|
|
|
|
|
110
2.79
|
0.784
1.99
|
186
277
|
|
403
600
|
890671 |
6
6
|
3.0
3.0
|
7
7
|
0.177
0.45
|
45
1.14
|
|
|
|
|
|
|
110
2.79
|
0.869
2.21
|
297
442
|
|
546
813
|
890672 |
4
4
|
3.0
3.0
|
7
7
|
0.225
0.57
|
45
1.14
|
|
|
|
|
|
|
110
2.79
|
0.917
2.33
|
441
656
|
|
703
1046
|
890673 |
2
2
|
3.0
3.0
|
7
7
|
0.282
0.72
|
45
1.14
|
|
|
|
|
|
|
60
1.52
|
1.045
2.65
|
702
1045
|
|
1043
1552
|
890702 |
1/0
1/0
|
3.0
3.0
|
19
19
|
0.361
0.92
|
55
1.40
|
|
|
|
|
|
|
80
2.03
|
1.261
3.20
|
1069
1591
|
|
1529
2275
|
890704 |
3/0
3/0
|
3.0
3.0
|
19
19
|
0.456
1.16
|
55
1.40
|
|
|
|
|
|
|
110
2.79
|
1.471
3.74
|
1699
2528
|
|
2262
3366
|
890705 |
4/0
4/0
|
3.0
3.0
|
19
19
|
0.512
1.30
|
55
1.40
|
|
|
|
|
|
|
110
2.79
|
1.553
3.94
|
2109
3139
|
|
2677
3984
|
890706 |
250
250
|
3.0
3.0
|
37
37
|
0.558
1.42
|
65
1.65
|
|
|
|
|
|
|
110
2.79
|
1.726
4.38
|
2469
3674
|
|
3179
4731
|
598118 |
600
600
|
3.0
3.0
|
61
61
|
0.865
2.20
|
80
2.03
|
|
|
|
|
|
|
110
2.79
|
2.425
6.16
|
6136
9131
|
|
7141
10627
|
Cond. Size (AWG/Kcmil) | Conductor Number | Min. Bend Radius (in) (cm) | Max Pull Tension (lbs) (kg) | DC Resistance @ 25C (ohms/1000') (ohms/km) | AC Resistance @ 75C (ohms/1000') (ohms/km) | Capacitive Reactance (Mohms x 1000ft) (Mohms x km) | Inductive Reactance (ohms/1000') (ohms/km) | Shield Short Circuit Current 6 Cycles (amps) | Raceway Ampacity @ 75C (amps) | Raceway Ampacity @ 90C (amps) | |
890670 |
8
8
|
3.0
3.0
|
3.1
7.87
|
396
179.62
|
0.653
0.97
|
0.786
1.17
|
|
0.052
0.08
|
|
50
50
|
55
55
|
890671 |
6
6
|
3.0
3.0
|
3.5
8.89
|
629
285.31
|
0.411
0.61
|
0.495
0.74
|
|
0.051
0.08
|
|
65
65
|
75
75
|
890672 |
4
4
|
3.0
3.0
|
3.7
9.40
|
1001
454.05
|
0.258
0.38
|
0.31
0.46
|
|
0.048
0.07
|
|
85
85
|
95
95
|
890673 |
2
2
|
3.0
3.0
|
5.2
13.21
|
1592
722.12
|
0.162
0.24
|
0.195
0.29
|
|
0.045
0.07
|
|
115
115
|
130
130
|
890702 |
1/0
1/0
|
3.0
3.0
|
6.3
16.00
|
2534
1149.40
|
0.102
0.15
|
0.122
0.18
|
|
0.044
0.07
|
|
150
150
|
170
170
|
890704 |
3/0
3/0
|
3.0
3.0
|
7.4
18.80
|
4027
1826.61
|
0.064
0.10
|
0.078
0.12
|
|
0.042
0.06
|
|
200
200
|
225
225
|
890705 |
4/0
4/0
|
3.0
3.0
|
7.8
19.81
|
5078
2303.34
|
0.051
0.08
|
0.062
0.09
|
|
0.041
0.06
|
|
230
230
|
260
260
|
890706 |
250
250
|
3.0
3.0
|
8.6
21.84
|
6000
2721.55
|
0.043
0.06
|
0.053
0.08
|
|
0.041
0.06
|
|
255
255
|
290
290
|
598118 |
600
600
|
3.0
3.0
|
14.6
37.08
|
14400
6531.72
|
0.018
0.03
|
0.025
0.04
|
|
0.039
0.06
|
|
420
420
|
475
475
|