CU FRXLPE PVC SHIELDED CONTROL CABLE

Control Cable 600 Volt Copper Conductors, Flame Retardant Cross Linked Polyethylene (FR-XLPE) Insulation Shielded Polyvinyl Chloride (PVC) Jacket, Control Cable Conductor Identification Method 1 Table 2. Silicone Free
Download Category Specifications:
PDF Excel Table

Application

Southwire’s 600 Volt control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. UL rated constructions can be used in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Only UL rated constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10.

Specifications

measurement
imperial metric
Select a set of products below for more information:
Conductor Ground Wire
No. of Conductors Size (AWG or kcmil) No. of Strands Insulation Thickness (mils) (mm) Size (AWG) No. of Strands Nom. OD (mils) (mm) Nominal Total Weight (lbs/1000') (kgs/km) Allowable Ampacity
618808 4 4 14 AWG 14 AWG 7 7 30 0.76 498 12.67 169 251
618809 7 7 14 AWG 14 AWG 7 7 30 0.76 604 15.36 249 371
618810 12 12 14 AWG 14 AWG 7 7 30 0.76 755 19.18 366 545
618811 19 19 14 AWG 14 AWG 7 7 30 0.76 910 23.11 550 818
662580 3 3 12 AWG 12 AWG 7 7 30 0.76 436 11.07 146 218
618813 4 4 12 AWG 12 AWG 7 7 30 0.76 571 14.51 193 287
618814 7 7 12 AWG 12 AWG 7 7 30 0.76 657 16.70 318 473
619611 12 12 12 AWG 12 AWG 7 7 30 0.76 876 22.26 540 803
618893 19 19 12 AWG 12 AWG 7 7 30 0.76 956 24.30 684 1018
606758 2 2 10 AWG 10 AWG 7 7 30 0.76 460 11.68 154 229
604107 3 3 10 AWG 10 AWG 7 7 30 0.76 487 12.38 199 296
604091 4 4 10 AWG 10 AWG 7 7 30 0.76 636 16.17 308 458
619547 5 5 10 AWG 10 AWG 7 7 30 0.76 609 15.49 304 453
618933 7 7 10 AWG 10 AWG 7 7 30 0.76 653 16.59 394 587
623305 8 8 10 AWG 10 AWG 7 7 30 0.76 714 18.14 448 667
606760 9 9 10 AWG 10 AWG 7 7 30 0.76 765 19.44 498 740
619618 12 12 10 AWG 10 AWG 7 7 30 0.76 974 24.74 735 1093
606689 4 4 8 AWG 8 AWG 7 7 45 1.14 708 17.99 417 620

Standards & References

  • ASTM B3 Standard Specification for Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 2
  • ICEA S-73-532 Standard for Control, Thermocouple Extension and Instrumentation Cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Vertical Tray Flame Test (70,000 Btu/hr) and ICEA T-29-520 - (210,000 Btu/hr)
  • VW-1 (Vertical-Wire) Flame Test

Construction

  • Conductor:7 strands class B compressed bare copper per ASTM B3 and ASTM B8
  • Insulation:Flame Retardant Cross Linked Polyethylene (FR-XLPE), 30 Mils thick for all cable sizes
  • Filler:Polypropylene filler on cables with 5 or less conductors
  • Binder:Polyester flat thread binder tape applied for cables with more than 5 conductors
  • Shielding:LCT 5 mils tape shield
  • Rip Chord:Rip chord for ease of jacket removal
  • Overall Jacket:Polyvinyl Chloride (PVC) Jacket
  • Color codes available upon request

Resources

There are no downloadable resources for this product.