CU PE/PVC SHIELDED CONTROL CABLE

Control Cable 600 Volt Copper Conductors, Polyethylene Polyvinyl Chloride (PE/PVC) Insulation Shielded Polyvinyl Chloride (PVC) Jacket, Control Cable Conductor Identification Method 1 Table 1. Silicone Free
Download Category Specifications:
PDF Excel Table

Application

Southwire’s 600 Volt control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. Only UL rated constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10.

Specifications

measurement
imperial metric
Select a set of products below for more information:
Conductor Ground Wire
No. of Conductors Size (AWG or kcmil) No. of Strands Insulation Thickness (mils) (mm) Size (AWG) No. of Strands Nom. OD (mils) (mm) Nominal Total Weight (lbs/1000') (kgs/km) Allowable Ampacity
618969 12 12 14 AWG 14 AWG 7 7 20 0.51 684 17.38 327 487
617106 12 12 12 AWG 12 AWG 7 7 20 0.51 810 20.59 468 697
606768 2 2 10 AWG 10 AWG 7 7 20 0.51 460 11.68 154 228
619162 3 3 10 AWG 10 AWG 7 7 20 0.51 487 12.38 194 289
616984 4 4 10 AWG 10 AWG 7 7 20 0.51 636 16.17 299 445
606769 5 5 10 AWG 10 AWG 7 7 20 0.51 609 15.49 300 447
622296 7 7 10 AWG 10 AWG 7 7 20 0.51 661 16.79 388 578
662472 8 8 10 AWG 10 AWG 7 7 20 0.51 796 20.23 495 736
606770 9 9 10 AWG 10 AWG 7 7 20 0.51 772 19.62 486 723
606771 12 12 10 AWG 10 AWG 7 7 20 0.51 907 23.06 657 977

Standards & References

  • ASTM B3 Standard Specification for Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 2
  • ICEA S-73-532 Standard for Control, Thermocouple Extension and Instrumentation Cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Vertical Tray Flame Test (70,000 Btu/hr) and ICEA T-29-520 - (210,000 Btu/hr)
  • VW-1 (Vertical-Wire) Flame Test

Construction

  • Conductor:7 strands class B compressed bare copper per ASTM B3 and ASTM B8
  • Insulation:Polyethylene (PE) 20 Mils thick and Polyvinyl Chloride (PVC) 10 Mils thick for all cable sizes
  • Filler:Polypropylene filler on cables with 5 or less conductors
  • Binder:Polyester flat thread binder tape applied for cables with more than 5 conductors
  • Shielding:5 mils tape shield
  • Rip Chord:Rip chord for ease of jacket removal
  • Overall Jacket:Polyvinyl Chloride (PVC) Jacket