TELCOFLEX® L2 Telecom Power Wire and Cable

Limited smoke, Non-halogenated Insulation, 105°C Dry, 60°C Wet
Download Category Specifications:
PDF Excel Table

Application

This specification covers the construction requirements for a limited smoke, non-halogenated power cable insulated with TelcoHyde® 5221. UL listed Type RHH, FT4-ST1 in accordance with the National Electrical Code. Product is for use in Central Office, CATV Head End, Data Center and Cell tower applications. Cable is suitable for UL “CT USE” (Cable Tray rated).

Specifications

measurement
imperial metric
Select a set of products below for more information:
Conductor Allowable Ampacities+
Size (AWG or kcmil) No. of Strands Nom. OD (Conductor) (mils) (mm) Nominal Total Weight (lbs/1000') (kgs/km) Allowable Ampacity at 75C Allowable Ampacity at 90C Insulation Thickness (mils) (mm) DC Resistance at 25°C
588680 14 AWG 14 AWG 41 41 26 39 20 20 25 25 45 1.14 2.73 2.73
588678 12 AWG 12 AWG 65 65 35 52 25 25 30 30 45 1.14 1.72 1.72
588676 10 AWG 10 AWG 104 104 49 74 35 35 40 40 45 1.14 1.08 1.08
569875 8 AWG 8 AWG 41 41 83 123 50 50 55 55 60 1.52 0.679 0.679
569858 6 AWG 6 AWG 65 65 117 174 65 65 75 75 60 1.52 0.436 0.436
569817 4 AWG 4 AWG 126 126 198 294 65 65 95 95 60 1.52 0.274 0.274
569745 2 AWG 2 AWG 168 168 252 375 115 115 130 130 60 1.52 0.172 0.172
569659 1/0 AWG 1/0 AWG 266 266 417 621 150 150 170 170 80 2.03 0.109 0.109
569770 2/0 AWG 2/0 AWG 342 342 525 782 175 175 195 195 80 2.03 0.0565 0.0565
569838 4/0 AWG 4/0 AWG 532 532 759 1130 230 230 260 260 80 2.03 0.0546 0.0546
569797 350 KCMIL 350 KCMIL 888 888 1265 1883 310 310 350 350 95 2.41 0.0334 0.0334
569626 500 KCMIL 500 KCMIL 1221 1221 1733 2579 95 2.41
569603 750 KCMIL 750 KCMIL 1850 1850 2713 4038 475 475 535 535 110 2.79 0.0157 0.0157

Standards & References

  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • ASTM B172 Standard Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Copper Conductors
  • UL 44 Type RHH, FT4-ST1, VW-1, 600 Volts DC or AC
  • UL 2731 Telecommunications Central Office Power Cable
  • CSA AWM IB 105°C 600V. FT4-ST1
  • IEC including 60674 and 60332
  • RoHS Complaint, Lead-Free, Silicone-Free
  • KS-24194™ List 2
  • ATIS-0600017.2014 Non-Halogenated DC Power Wire and Cable for Telecommunications Power Systems
  • Telcordia GR-347-CORE
  • REACH - European Community Regulation

Construction

  • Conductor:Class K (14-10 AWG), Class I modified bunched (8 and 6 AWG) or rope bunched (4 AWG and larger) tinned copper
  • Separator:Opaque Mylar tape
  • Insulation:Limited smoke, non-halogenated, 105°C Dry, 60°C Wet TelcoHyde® 5221. Conforms to UL 44, UL 758, CSA C22.2 No. 210-11, and Telcordia Specification GR-347- CORE. Insulation has a Limiting Oxygen Index of 35%