This specification covers the construction requirements for a limited smoke, non-halogenated power cable insulated with TelcoHyde® 5221 with an overall flame retardant saturated braid. UL listed Type RHH, FT4-ST1 in accordance with the National Electrical Code. Product is for use in Central Office, CATV Head End, Data Center and Cell Tower applications. Cable is suitable for UL “CT USE” (Cable Tray rated).
Conductor | Allowable Ampacities+ | ||||||
Size (AWG or kcmil) (mm2) | No. of Strands | Nominal Total Weight (lbs/1000') (kgs/km) | Allowable Ampacity at 75C | Allowable Ampacity at 90C | Insulation Thickness (mils) (mm) | DC Resistance at 25°C | |
More Options |
14 AWG
14 AWG
|
7
7
|
36
54
|
20
20
|
25
25
|
45
1.14
|
2.73
2.73
|
More Options |
12 AWG
12 AWG
|
7
7
|
45
67
|
25
25
|
30
30
|
45
1.14
|
1.72
1.72
|
More Options |
10 AWG
10 AWG
|
7
7
|
62
92
|
35
35
|
40
40
|
45
1.14
|
1.08
1.08
|
More Options |
8 AWG
8 AWG
|
7
7
|
96
143
|
50
50
|
55
55
|
60
1.52
|
0.6795
0.6795
|
More Options |
6 AWG
6 AWG
|
7
7
|
132
197
|
65
65
|
75
75
|
60
1.52
|
0.4276
0.4276
|
More Options |
4 AWG
4 AWG
|
7
7
|
185
275
|
85
85
|
95
95
|
60
1.52
|
0.2689
0.2689
|
More Options |
2 AWG
2 AWG
|
7
7
|
279
416
|
|
|
60
1.52
|
|
More Options |
1 AWG
1 AWG
|
19
19
|
363
540
|
|
|
80
2.03
|
|
More Options |
1/0 AWG
1/0 AWG
|
19
19
|
442
657
|
150
150
|
170
170
|
80
2.03
|
0.1063
0.1063
|
More Options |
2/0 AWG
2/0 AWG
|
19
19
|
529
787
|
175
175
|
195
195
|
80
2.03
|
0.08432
0.08432
|
More Options |
4/0 AWG
4/0 AWG
|
19
19
|
796
1184
|
230
230
|
260
260
|
80
2.03
|
0.05248
0.05248
|
More Options |
350 KCMIL
350 KCMIL
|
37
37
|
1288
1917
|
|
|
95
2.41
|
|
More Options |
500 KCMIL
500 KCMIL
|
37
37
|
1783
2654
|
|
|
95
2.41
|
|
More Options |
750 KCMIL
750 KCMIL
|
61
61
|
2638
3926
|
475
475
|
535
535
|
110
2.79
|
0.01481
0.01481
|