Southwire’s 600 Volt Type MC power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of op- erating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. The ground is sized to 50% of the phase conductor with three separate bare grounds one in each interstecie between condutors. Silicone Free.
Cond. Size | 750 KCMIL 750 KCMIL | |
Cond. Strands | 58 58 | |
Diameter Over Conductor (in) (cm) | 0.908 2.31 | inch cm |
Inner Layer Thickness (mils) (mm) | 80 2.03 | mils mm |
Diameter Over Armor (in) (cm) | 2.624 6.66 | inch cm |
Outer Layer Thickness (mils) (mm) | 80 2.03 | mils mm |
Approx. OD (in) (cm) | 2.790 7.09 | inch cm |
Approx. Weight (lbs/1000') (kgs/km) | 4071 6058 | lbs/1000' kgs/km |
Max Pull Tension (lbs) (kg) | 13500 6123.49 | lbs kg |
Min. Bend Radius (in) (cm) | 19.5 49.53 | inch cm |
* Strand count meets minimum number per ASTM