APPLICATION
Southwire SIMpull® THHN Aluminum Wire & Cable with Alumaflex® Brand conductors are primarily used in conduit and cable trays for services, feeders, and branch circuits in commercial or industrial applications as specified in the National Electrical Code and other applicable codes and standards. Voltage for all applications is 600 volts. SIMpull® THHN/THWN-2 aluminum conductors are designed to be installed without the application of a pulling lubricant. These conductors have multiple ratings depending on the product application. Allowable temperatures are as follows:
- THHN or T90 Nylon- Dry locations not to exceed 90°C
- THWN-2 Wet or dry locations not to exceed 90°C or locations not to exceed 75°C when exposed to oil
- TWN75 Wet locations not to exceed 75°C
FEATURES
- Sunlight Resistant- Sizes #2 and larger
- Oil and Gasoline Resistant II
- CT- Sizes 1/0 AWG and larger
- VW-1 All Sizes
- FT1 All Sizes
- T90 Nylon on all sizes
- TWN75 All sizes
- National Electrical Code, NFPA
- NEMA WC-70 Construction Requirements
- RoHS Compliant
Cond. Size | Conductor Number | Cond. Strands | Diameter Over Conductor (in) (cm) | Inner Layer Thickness (mils) (mm) | Outer Layer Thickness (mils) (mm) | Approx. OD (in) (cm) | Aluminum Weight (lbs/1000') (kgs/km) | Approx. Weight (lbs/1000') (kgs/km) | |
More Options |
6 AWG
6 AWG
|
0.0
0.0
|
7
7
|
0.169
0.43
|
30
0.76
|
6
0.15
|
0.243
0.62
|
24
36
|
39
58
|
More Options |
4 AWG
4 AWG
|
1
1
|
7
7
|
0.212
0.54
|
40
1.02
|
7
0.18
|
0.309
0.78
|
39
58
|
63
94
|
More Options |
2 AWG
2 AWG
|
1
1
|
6
6
|
0.268
0.68
|
40
1.02
|
7
0.18
|
0.364
0.92
|
62
92
|
92
137
|
More Options |
1 AWG
1 AWG
|
1
1
|
8
8
|
0.298
0.76
|
50
1.27
|
8
0.20
|
0.417
1.06
|
78
116
|
118
176
|
More Options |
1/0 AWG
1/0 AWG
|
1
1
|
10
10
|
0.336
0.85
|
50
1.27
|
8
0.20
|
0.456
1.16
|
99
147
|
143
213
|
More Options |
2/0 AWG
2/0 AWG
|
1
1
|
12
12
|
0.376
0.96
|
50
1.27
|
8
0.20
|
0.496
1.26
|
125
186
|
174
259
|
More Options |
3/0 AWG
3/0 AWG
|
1
1
|
15
15
|
0.422
1.07
|
50
1.27
|
8
0.20
|
0.543
1.38
|
158
235
|
213
317
|
More Options |
3/0 AWG
3/0 AWG
|
1
1
|
16
16
|
0.422
1.07
|
50
1.27
|
5
0.13
|
0.543
1.38
|
158
235
|
213
317
|
More Options |
4/0 AWG
4/0 AWG
|
1
1
|
19
19
|
0.474
1.20
|
50
1.27
|
8
0.20
|
0.595
1.51
|
199
296
|
261
388
|
More Options |
250 KCMIL
250 KCMIL
|
1
1
|
22
22
|
0.520
1.32
|
60
1.52
|
9
0.23
|
0.662
1.68
|
235
350
|
314
467
|
More Options |
300 KCMIL
300 KCMIL
|
1
1
|
21
21
|
0.569
1.45
|
60
1.52
|
9
0.23
|
0.712
1.81
|
282
420
|
372
554
|
More Options |
350 KCMIL
350 KCMIL
|
1
1
|
35
35
|
0.615
1.56
|
60
1.52
|
9
0.23
|
0.758
1.93
|
329
490
|
424
631
|
More Options |
400 KCMIL
400 KCMIL
|
1
1
|
35
35
|
0.659
1.67
|
60
1.52
|
9
0.23
|
0.801
2.03
|
376
560
|
475
707
|
More Options |
500 KCMIL
500 KCMIL
|
1
1
|
35
35
|
0.735
1.87
|
60
1.52
|
9
0.23
|
0.878
2.23
|
471
701
|
581
865
|
More Options |
600 KCMIL
600 KCMIL
|
1
1
|
58
58
|
0.812
2.06
|
70
1.78
|
10
0.25
|
0.969
2.46
|
565
841
|
704
1048
|
More Options |
700 KCMIL
700 KCMIL
|
1
1
|
58
58
|
0.877
2.23
|
70
1.78
|
10
0.25
|
1.041
2.64
|
659
981
|
811
1207
|
More Options |
750 KCMIL
750 KCMIL
|
1
1
|
58
58
|
0.908
2.31
|
70
1.78
|
10
0.25
|
1.072
2.72
|
706
1051
|
867
1290
|
More Options |
750 KCMIL
750 KCMIL
|
1
1
|
58
58
|
0.908
2.31
|
70
1.78
|
10
0.25
|
1.072
2.72
|
706
1051
|
867
1290
|
More Options |
900 KCMIL
900 KCMIL
|
1
1
|
58
58
|
0.999
2.54
|
70
1.78
|
10
0.25
|
1.163
2.95
|
847
1260
|
1034
1539
|
More Options |
1000 KCMIL
1000 KCMIL
|
1
1
|
58
58
|
1.060
2.69
|
70
1.78
|
10
0.25
|
1.224
3.11
|
941
1400
|
1124
1673
|
* Strand count meets minimum number per ASTM
Cond. Size | Conductor Number | Min. Bend Radius (in) (cm) | Max Pull Tension (lbs) (kg) | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | Allowable Ampacity Raceway 75C | Allowable Ampacity Raceway 90C | |
More Options |
6 AWG
6 AWG
|
0.0
0.0
|
1.0
2.54
|
157
71.21
|
0.674
1.00
|
0.812
1.21
|
0.051
0.08
|
50
50
|
55
55
|
More Options |
4 AWG
4 AWG
|
1
1
|
1.2
3.05
|
250
113.40
|
0.424
0.63
|
0.510
0.76
|
0.048
0.07
|
65
65
|
75
75
|
More Options |
2 AWG
2 AWG
|
1
1
|
1.5
3.81
|
398
180.53
|
0.267
0.40
|
0.321
0.48
|
0.045
0.07
|
90
90
|
100
100
|
More Options |
1 AWG
1 AWG
|
1
1
|
1.7
4.32
|
502
227.70
|
0.211
0.31
|
0.254
0.38
|
0.046
0.07
|
100
100
|
115
115
|
More Options |
1/0 AWG
1/0 AWG
|
1
1
|
1.8
4.57
|
633
287.12
|
0.168
0.25
|
0.201
0.30
|
0.044
0.07
|
120
120
|
135
135
|
More Options |
2/0 AWG
2/0 AWG
|
1
1
|
2.0
5.08
|
798
361.97
|
0.133
0.20
|
0.160
0.24
|
0.043
0.06
|
135
135
|
150
150
|
More Options |
3/0 AWG
3/0 AWG
|
1
1
|
2.2
5.59
|
1006
456.31
|
0.105
0.16
|
0.126
0.19
|
0.042
0.06
|
155
155
|
175
175
|
More Options |
3/0 AWG
3/0 AWG
|
1
1
|
2.2
5.59
|
1006
456.31
|
0.105
0.16
|
0.126
0.19
|
0.042
0.06
|
155
155
|
175
175
|
More Options |
4/0 AWG
4/0 AWG
|
1
1
|
2.4
6.10
|
1269
575.61
|
0.084
0.13
|
0.100
0.15
|
0.041
0.06
|
180
180
|
205
205
|
More Options |
250 KCMIL
250 KCMIL
|
1
1
|
2.6
6.60
|
1500
680.39
|
0.071
0.11
|
0.086
0.13
|
0.041
0.06
|
205
205
|
230
230
|
More Options |
300 KCMIL
300 KCMIL
|
1
1
|
2.8
7.11
|
1800
816.47
|
0.059
0.09
|
0.071
0.11
|
0.041
0.06
|
230
230
|
260
260
|
More Options |
350 KCMIL
350 KCMIL
|
1
1
|
3.0
7.62
|
2100
952.54
|
0.050
0.07
|
0.062
0.09
|
0.040
0.06
|
250
250
|
280
280
|
More Options |
400 KCMIL
400 KCMIL
|
1
1
|
3.2
8.13
|
2400
1088.62
|
0.044
0.07
|
0.054
0.08
|
0.040
0.06
|
270
270
|
305
305
|
More Options |
500 KCMIL
500 KCMIL
|
1
1
|
3.5
8.89
|
3000
1360.78
|
0.035
0.05
|
0.044
0.07
|
0.039
0.06
|
310
310
|
350
350
|
More Options |
600 KCMIL
600 KCMIL
|
1
1
|
3.9
9.91
|
3600
1632.93
|
0.029
0.04
|
0.037
0.06
|
0.039
0.06
|
340
340
|
385
385
|
More Options |
700 KCMIL
700 KCMIL
|
1
1
|
5.2
13.21
|
4200
1905.09
|
0.025
0.04
|
0.033
0.05
|
0.038
0.06
|
375
375
|
425
425
|
More Options |
750 KCMIL
750 KCMIL
|
1
1
|
5.4
13.72
|
4500
2041.16
|
0.024
0.04
|
0.031
0.05
|
0.038
0.06
|
385
385
|
435
435
|
More Options |
750 KCMIL
750 KCMIL
|
1
1
|
5.4
13.72
|
4500
2041.16
|
0.024
0.04
|
0.031
0.05
|
0.038
0.06
|
385
385
|
435
435
|
More Options |
900 KCMIL
900 KCMIL
|
1
1
|
5.8
14.73
|
5400
2449.40
|
0.020
0.03
|
0.027
0.04
|
0.037
0.06
|
425
425
|
480
480
|
More Options |
1000 KCMIL
1000 KCMIL
|
1
1
|
6.1
15.49
|
6000
2721.55
|
0.018
0.03
|
0.025
0.04
|
0.037
0.06
|
445
445
|
500
500
|
* Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
* Inductive Reactance is based on non-ferrous conduit with one diameter spacing center-to-center.
Size (strand) | Gray | Green | Purple | Pink | Tan | Gray/Purple | Gray/Orange |
6 (7)
6 (7)
|
|
566358 |
|
|
|
|
|
4 (7)
4 (7)
|
|
562211 |
|
|
|
|
|
2 (6)
2 (6)
|
578329 | 562745 |
|
|
|
|
|
1 (8)
1 (8)
|
578327 | 562746 |
|
|
|
|
|
1/0 (10)
1/0 (10)
|
562755 | 562756 | 573380 |
|
|
|
|
2/0 (10)
2/0 (10)
|
562760 | 562761 |
573370
573370
|
|
|
|
|
3/0 (10)
3/0 (10)
|
562765 | 562766 | 573371 | 671296 | 671192 | 671310 |
|
4/0 (19)
4/0 (19)
|
562767 | 562768 |
573372
573372
|
|
|
|
|
250 (22)
250 (22)
|
561866 | 561867 | 573373 | 581834 | 581833 |
|
|
300 (21)
300 (21)
|
562773 | 562774 | 573374 |
|
|
|
|
350 (35)
350 (35)
|
561862 | 562775 | 573375 | 641125 | 641127 |
|
669737 |
400 (35)
400 (35)
|
562783 | 562699 | 573376 | 678467 | 674297 |
|
|
500 (34)
500 (34)
|
561856 | 561857 | 573377 | 584173 | 584172 |
|
675375 |
600 (58)
600 (58)
|
561850 | 561851 | 573379 | 589106 |
|
|
|
700 (58)
700 (58)
|
562693 |
|
671948 | 671945 | 671674 |
|
|
750 (58)
750 (58)
|
561841 | 561842 | 573481 | 590187 |
|
|
|
900 (58)
900 (58)
|
561786 | 562684 |
|
|
|
|
|
1000 (58)
1000 (58)
|
564283
564283
|
564281 |
|
|
|
|
|