Southwire’s 600 Volt Type MC-HL ARMOR-X® power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, 250°C for short circuit conditions, and -50°C for cold bend. For uses in Class I, II, and III, Division 1 and 2 hazardous locations per NEC Article 501, 502, and 503.
Cond. Size | Cond. Strands | Diameter Over Conductor (in) (cm) | Inner Layer Thickness (mils) (mm) | Diameter Over Armor (in) (cm) | Outer Layer Thickness (mils) (mm) | Approx. OD (in) (cm) | Approx. Weight (lbs/1000') (kgs/km) | Max Pull Tension (lbs) (kg) | Min. Bend Radius (in) (cm) | |
More Options |
8 AWG
8 AWG
|
7
7
|
0.141
0.36
|
45
1.14
|
0.840
2.13
|
50
1.27
|
0.946
2.40
|
476
708
|
422
191.42
|
6.6
16.76
|
More Options |
6 AWG
6 AWG
|
7
7
|
0.177
0.45
|
45
1.14
|
0.920
2.34
|
50
1.27
|
1.026
2.61
|
649
966
|
671
304.36
|
7.2
18.29
|
More Options |
4 AWG
4 AWG
|
7
7
|
0.225
0.57
|
45
1.14
|
1.060
2.69
|
50
1.27
|
1.166
2.96
|
918
1366
|
1068
484.44
|
8.2
20.83
|
More Options |
2 AWG
2 AWG
|
7
7
|
0.282
0.72
|
45
1.14
|
1.220
3.10
|
60
1.52
|
1.326
3.37
|
1295
1927
|
1698
770.20
|
9.3
23.62
|
More Options |
1/0 AWG
1/0 AWG
|
19
19
|
0.361
0.92
|
55
1.40
|
1.470
3.73
|
60
1.52
|
1.576
4.00
|
1948
2899
|
2703
1226.06
|
11.0
27.94
|
More Options |
2/0 AWG
2/0 AWG
|
19
19
|
0.405
1.03
|
55
1.40
|
1.540
3.91
|
60
1.52
|
1.666
4.23
|
2436
3625
|
3407
1545.39
|
11.7
29.72
|
More Options |
3/0 AWG
3/0 AWG
|
19
19
|
0.456
1.16
|
55
1.40
|
1.760
4.47
|
60
1.52
|
1.886
4.79
|
2954
4396
|
4295
1948.18
|
13.2
33.53
|
More Options |
4/0 AWG
4/0 AWG
|
19
19
|
0.512
1.30
|
55
1.40
|
1.845
4.69
|
60
1.52
|
1.971
5.01
|
3536
5262
|
5416
2456.65
|
13.8
35.05
|
More Options |
250 KCMIL
250 KCMIL
|
37
37
|
0.558
1.42
|
65
1.65
|
2.040
5.18
|
60
1.52
|
2.166
5.50
|
4278
6366
|
6400
2902.99
|
15.2
38.61
|
More Options |
350 KCMIL
350 KCMIL
|
37
37
|
0.661
1.68
|
65
1.65
|
2.290
5.82
|
75
1.91
|
2.448
6.22
|
5741
8544
|
8960
4064.18
|
17.1
43.43
|
More Options |
500 KCMIL
500 KCMIL
|
37
37
|
0.789
2.00
|
65
1.65
|
2.670
6.78
|
75
1.91
|
2.828
7.18
|
7980
11876
|
12800
5805.98
|
19.8
50.29
|
More Options |
750 KCMIL
750 KCMIL
|
61
61
|
0.968
2.46
|
80
2.03
|
3.220
8.18
|
85
2.16
|
3.398
8.63
|
12254
18236
|
19200
8708.97
|
23.8
60.45
|
Cond. Size | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Capacitive Reactance (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | |
More Options |
8 AWG
8 AWG
|
0.653
0.97
|
0.786
1.17
|
0.033
0.05
|
0.052
0.08
|
More Options |
6 AWG
6 AWG
|
0.411
0.61
|
0.495
0.74
|
0.027
0.04
|
0.051
0.08
|
More Options |
4 AWG
4 AWG
|
0.258
0.38
|
0.310
0.46
|
0.022
0.03
|
0.048
0.07
|
More Options |
2 AWG
2 AWG
|
0.162
0.24
|
0.195
0.29
|
0.018
0.03
|
0.045
0.07
|
More Options |
1/0 AWG
1/0 AWG
|
0.102
0.15
|
0.122
0.18
|
0.017
0.03
|
0.044
0.07
|
More Options |
2/0 AWG
2/0 AWG
|
0.081
0.12
|
0.097
0.14
|
0.016
0.02
|
0.043
0.06
|
More Options |
3/0 AWG
3/0 AWG
|
0.064
0.10
|
0.078
0.12
|
0.014
0.02
|
0.042
0.06
|
More Options |
4/0 AWG
4/0 AWG
|
0.051
0.08
|
0.062
0.09
|
0.013
0.02
|
0.041
0.06
|
More Options |
250 KCMIL
250 KCMIL
|
0.043
0.06
|
0.053
0.08
|
0.014
0.02
|
0.041
0.06
|
More Options |
350 KCMIL
350 KCMIL
|
0.031
0.05
|
0.039
0.06
|
0.012
0.02
|
0.040
0.06
|
More Options |
500 KCMIL
500 KCMIL
|
0.022
0.03
|
0.029
0.04
|
0.010
0.01
|
0.039
0.06
|
More Options |
750 KCMIL
750 KCMIL
|
0.014
0.02
|
0.022
0.03
|
0.010
0.01
|
0.038
0.06
|
* Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.