Southwire's 5kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
Stock # | 56891899 56891899 | |
Cond. Size (AWG/Kcmil) | 250 250 | |
Cond. Strands | 37 37 | |
Diameter Over Conductor (in) (cm) | 0.558 1.42 | inch cm |
Diameter Over Insulation (in) (cm) | 0.768 1.95 | inch cm |
Insulation Thickness (mils) (mm) | 90 2.29 | mils mm |
Diameter Over Shield (in) (cm) | 0.828 2.10 | inch cm |
Inner Jacket Thickness (mils) (mm) | 110 2.79 | mils mm |
Diameter Over Armor (in) (cm) | 2.402 6.10 | inch cm |
Jacket Thickness (mils) (mm) | 75 1.91 | mils mm |
Approx. OD (in) (cm) | 2.552 6.48 | inch cm |
Approx. Weight (lbs/1000') (kgs/km) | 4663 6939 | lbs/1000' kgs/km |
Max Pull Tension (lbs) (kg) | 6000 2721.55 | lbs kg |
Min. Bend Radius (in) (cm) | 17.9 45.47 | inch cm |