AAC

All Aluminum Conductor. Bare.
Download Category Specifications:
PDF Excel Table

Application

AAC-All Aluminum Conductor, Bare

Specifications

measurement
imperial metric
Select a set of products below for more information:
Conductor
No. of Conductors Size (AWG or kcmil) No. of Strands Nom. OD (mils) (mm) Nominal Total Weight (lbs/1000') (kgs/km) Allowable Ampacity
100800 1 1 6 AWG 6 AWG 7 7 183 4.66 25 37
100818 1 1 4 AWG 4 AWG 7 7 231 5.88 39 58
100834 1 1 2 AWG 2 AWG 7 7 292 7.42 62 93
100859 1 1 1/0 AWG 1/0 AWG 7 7 368 9.36 99 147
100867 1 1 2/0 AWG 2/0 AWG 7 7 413 10.51 125 186
100875 1 1 3/0 AWG 3/0 AWG 7 7 464 11.80 157 234
100883 1 1 4/0 AWG 4/0 AWG 7 7 521 13.25 198 295
227884 1 1 250 KCMIL 250 KCMIL 19 19 573 14.57 234 349
100891 1 1 266.8 KCMIL 266.8 KCMIL 7 7 585 14.88 250 372
100917 1 1 336.4 KCMIL 336.4 KCMIL 19 19 665 16.90 316 471
148122 1 1 350 KCMIL 350 KCMIL 19 19 678 17.23 328 488
100925 1 1 397.5 KCMIL 397.5 KCMIL 19 19 723 18.37 373 555
100933 1 1 477 KCMIL 477 KCMIL 19 19 792 20.12 447 665
151258 1 1 500 KCMIL 500 KCMIL 37 37 813 20.66 468 697
100941 1 1 556.5 KCMIL 556.5 KCMIL 19 19 855 21.73 523 778
157743 1 1 600 KCMIL 600 KCMIL 37 37 891 22.63 562 836
100974 1 1 636 KCMIL 636 KCMIL 37 37 917 23.31 596 887
100982 1 1 715.5 KCMIL 715.5 KCMIL 37 37 973 24.73 671 999
182618 1 1 750 KCMIL 750 KCMIL 37 37 996 25.32 703 1047
100990 1 1 795 KCMIL 795 KCMIL 37 37 1026 26.07 745 1109
101013 1 1 900 KCMIL 900 KCMIL 37 37 1092 27.74 844 1256
101014 1 1 954 KCMIL 954 KCMIL 37 37 1124 28.55 894 1331
101022 1 1 1033.5 KCMIL 1033.5 KCMIL 37 37 1169 29.71 971 1444
101089 1 1 1113 KCMIL 1113 KCMIL 61 61 1215 30.88 1044 1553
101097 1 1 1192.5 KCMIL 1192.5 KCMIL 61 61 1258 31.96 1117 1663
101105 1 1 1272 KCMIL 1272 KCMIL 61 61 1299 33.01 1192 1774
101113 1 1 1351 KCMIL 1351 KCMIL 61 61 1339 34.02 1266 1884
101121 1 1 1431 KCMIL 1431 KCMIL 61 61 1378 35.02 1342 1997
101147 1 1 1590 KCMIL 1590 KCMIL 61 61 1452 36.90 1489 2216
182634 1 1 1750 KCMIL 1750 KCMIL 61 61 1524 38.72 1641 2442
182642 1 1 2000 KCMIL 2000 KCMIL 91 91 1630 41.41 1873 2788
157149 1 1 2250 KCMIL 2250 KCMIL 91 91 1729 43.92 2128 3167
332924 1 1 2300 KCMIL 2300 KCMIL 61 61 1747 44.39 2177 3240
182675 1 1 2500 KCMIL 2500 KCMIL 91 91 1822 46.30 2365 3519
258889 1 1 3000 KCMIL 3000 KCMIL 127 127 1998 50.75 2840 4226
611748 1 1 3500 KCMIL 3500 KCMIL 127 127 2158 54.81 3344 4977
267070 1 1 52.79 MMSQ 52.79 MMSQ 7 7 366 9.30 98 145

Standards & References

Southwire's AAC bare conductor meets or exceeds the following ASTM specifications:

  • B230 Aluminum 1350-H19 Wire for Electrical Purposes.
  • B231 Concentric-Lay-Stranded Aluminum 1350 Conductors.

Construction

Aluminum 1350-H19 wires, concentrically stranded.