Southwire® SIMpull XHHW-2® copper conductors are primarily used in conduit, Cable Tray or other recognized raceways for services, feeders, and branch circuit wiring, as specified in the National Electrical Code. SIMpull XHHW-2® copper conductors may be used in wet or dry locations at temperatures not to exceed 90° C. Voltage rating for XHHW-2 conductors is 600 volts for all sizes and 1000 volts for sizes 8 AWG and larger. Suitable for use in Health Care Facilities per Section 517.160 of the National Electrical Code where a dielectric constant of less than 3.5 maybe specified. This cable is designed to be installed without the application of pulling lubricant.
Conductor | Allowable Ampacities+ | ||||||||
Size (AWG or kcmil) (mm2) | No. of Conductors | No. of Strands | Nom. OD (mils) (mm) | Insulation Thickness (mils) (mm) | Nominal Total Weight (lbs/1000') (kgs/km) | Allowable Ampacity at 60C | Allowable Ampacity at 75C | Allowable Ampacity at 90C | |
112920 |
14 AWG
14 AWG
|
1
1
|
7
7
|
135
3.43
|
30
0.76
|
17
26
|
15
15
|
15
15
|
15
15
|
550220 |
12 AWG
12 AWG
|
1
1
|
1
1
|
144
3.68
|
30
0.76
|
25
37
|
20
20
|
20
20
|
20
20
|
112938 |
12 AWG
12 AWG
|
1
1
|
7
7
|
151
3.84
|
30
0.76
|
26
38
|
20
20
|
20
20
|
20
20
|
137240 |
10 AWG
10 AWG
|
1
1
|
1
1
|
165
4.21
|
30
0.76
|
37
55
|
30
30
|
30
30
|
30
30
|
112946 |
10 AWG
10 AWG
|
1
1
|
7
7
|
177
4.50
|
30
0.76
|
39
58
|
30
30
|
30
30
|
30
30
|
112953 |
8 AWG
8 AWG
|
1
1
|
7
7
|
238
6.05
|
45
1.14
|
64
95
|
40
40
|
50
50
|
55
55
|
112961 |
6 AWG
6 AWG
|
1
1
|
7
7
|
274
6.96
|
45
1.14
|
97
144
|
55
55
|
65
65
|
75
75
|
112979 |
4 AWG
4 AWG
|
1
1
|
7
7
|
321
8.15
|
45
1.14
|
148
220
|
70
70
|
85
85
|
95
95
|
267278 |
3 AWG
3 AWG
|
1
1
|
7
7
|
348
8.84
|
45
1.14
|
184
273
|
85
85
|
100
100
|
115
115
|
112987 |
2 AWG
2 AWG
|
1
1
|
7
7
|
379
9.63
|
45
1.14
|
228
340
|
95
95
|
115
115
|
130
130
|
112995 |
1 AWG
1 AWG
|
1
1
|
19
19
|
437
11.10
|
55
1.40
|
290
432
|
110
110
|
130
130
|
145
145
|
113001 |
1/0 AWG
1/0 AWG
|
1
1
|
19
19
|
476
12.09
|
55
1.40
|
362
538
|
125
125
|
150
150
|
170
170
|
113019 |
2/0 AWG
2/0 AWG
|
1
1
|
19
19
|
520
13.21
|
55
1.40
|
450
670
|
145
145
|
175
175
|
195
195
|
113027 |
3/0 AWG
3/0 AWG
|
1
1
|
19
19
|
570
14.48
|
55
1.40
|
562
836
|
165
165
|
200
200
|
225
225
|
113035 |
4/0 AWG
4/0 AWG
|
1
1
|
19
19
|
626
15.90
|
55
1.40
|
704
1048
|
195
195
|
230
230
|
260
260
|
113043 |
250 KCMIL
250 KCMIL
|
1
1
|
37
37
|
696
17.68
|
65
1.65
|
835
1242
|
215
215
|
255
255
|
290
290
|
113050 |
300 KCMIL
300 KCMIL
|
1
1
|
37
37
|
753
19.13
|
67
1.70
|
998
1485
|
240
240
|
285
285
|
320
320
|
113068 |
350 KCMIL
350 KCMIL
|
1
1
|
37
37
|
799
20.29
|
65
1.65
|
1154
1717
|
260
260
|
310
310
|
350
350
|
113076 |
400 KCMIL
400 KCMIL
|
1
1
|
37
37
|
823
20.90
|
65
1.65
|
1311
1951
|
280
280
|
335
335
|
380
380
|
113084 |
500 KCMIL
500 KCMIL
|
1
1
|
37
37
|
904
22.96
|
65
1.65
|
1628
2423
|
320
320
|
380
380
|
430
430
|
113092 |
600 KCMIL
600 KCMIL
|
1
1
|
61
61
|
1008
25.60
|
80
2.03
|
1964
2923
|
350
350
|
420
420
|
475
475
|
586272 |
700 KCMIL
700 KCMIL
|
1
1
|
61
61
|
1103
28.02
|
80
2.03
|
2284
3400
|
385
385
|
460
460
|
520
520
|
113100 |
750 KCMIL
750 KCMIL
|
1
1
|
61
61
|
1107
28.12
|
80
2.03
|
2439
3630
|
400
400
|
475
475
|
535
535
|
113134 |
1000 KCMIL
1000 KCMIL
|
1
1
|
61
61
|
1285
32.64
|
80
2.03
|
3237
4817
|
455
455
|
545
545
|
615
615
|
Southwire® SIMpull XHHW-2® copper conductors comply with the following:
Southwire® SIMpull XHHW-2® copper conductors are annealed (soft) copper. Insulation is an abrasion, moisture, and heat resistant thermoset cross-linked polyethylene (XLPE). Conductor sizes 8 AWG and larger are marked sunlight resistant. Colors are available and may be subject to economic order quantity.