Southwire’s Airport Lighting Cable meets the requirements of (FAA) L-824 C underground electrical cable for airport lighting circuits (AC 150/5345-53D), (AC 150/5345-7F). Southwire’s Airport Lighting Cable is available in sizes #8 AWG through #4 AWG 7 strands. The conductors are bare annealed copper class B and covered with an abrasion, moisture, and heat resistant Cross-Linked Polyethylene XLPE insulation. The 5KV non-shielded cable is available in Black, Red and Yellow colors. Southwire Airport Lighting Cable is primarily used for series lighting circuits for runways, control systems, and other multi-purpose installations. It can be used in direct burial, conduit, or raceways. These cables are capable of operating continuously at a conductor temperature not in excess of 90°C for normal operation, 130°C for emergency and 250°C for short circuit conditions. Silicone Free.<br> <br> • Cable is manufactured by Southwire Company in either Starkville, MS or Douglas, GA USA<br> • Cable has a warranty of 1 year from date of installation or 2 years from date of shipment whichever comes first.
Cond. Size (AWG/Kcmil) | Cond. Strands | Insulation Thickness (mils) (mm) | Approx. OD (in) (cm) | Approx. Weight (lbs/1000') (kgs/km) | Min. Bend Radius (in) (cm) | |
More Options |
8
8
|
7
7
|
110
2.79
|
0.375
0.95
|
90
134
|
3.00
7.62
|
More Options |
6
6
|
7
7
|
110
2.79
|
0.415
1.05
|
189
281
|
3.32
8.43
|
More Options |
4
4
|
7
7
|
110
2.79
|
0.460
1.17
|
271
403
|
3.68
9.35
|
Cond. Size (AWG/Kcmil) | |
More Options |
8
8
|
More Options |
6
6
|
More Options |
4
4
|