Type MC Cable - "flame retardant sunlight resistant PVC Jacket" is suitable for use as follows:
Conductor | Ground Wire | ||||||||
No. of Conductors | Size (AWG or kcmil) (mm2) | No. of Strands | Insulation Thickness (mils) (mm) | Size (AWG) | No. of Strands | Nom. OD (mils) (mm) | Nominal Total Weight (lbs/1000') (kgs/km) | Allowable Ampacity | |
552465 |
3
3
|
2/0 AWG
2/0 AWG
|
12
12
|
50
1.27
|
4
4
|
|
1386
35.21
|
847
1260
|
|
552464 |
3
3
|
3/0 AWG
3/0 AWG
|
16
16
|
50
1.27
|
4
4
|
|
1477
37.54
|
969
1441
|
|
552484 |
3
3
|
4/0 AWG
4/0 AWG
|
19
19
|
50
1.27
|
2
2
|
|
1722
43.74
|
1297
1931
|
|
554283 |
4
4
|
4/0 AWG
4/0 AWG
|
19
19
|
50
1.27
|
2
2
|
|
1881
47.79
|
1649
2453
|
|
555809 |
3
3
|
500 KCMIL
500 KCMIL
|
35
35
|
60
1.52
|
1
1
|
|
2333
59.27
|
2467
3671
|
|
560767 |
4
4
|
500 KCMIL
500 KCMIL
|
34
34
|
60
1.52
|
3/0
3/0
|
|
2589
65.76
|
3348
4982
|
|
560770 |
4
4
|
600 KCMIL
600 KCMIL
|
41
41
|
70
1.78
|
3/0
3/0
|
|
2808
71.34
|
3943
5868
|
|
Southwire AlumaFlex™ Type MC Cable - PVC Jacketed meets or exceeds the following requirements:
Southwire AlumaFlex™ Type MC Cable with Triple E™ Aluminum Alloy - PVC Jacketed is constructed with Aluminum Type THHN/THWN-2 conductors rated 90°C wet or dry, and a bare aluminum grounding conductor for sizes 1/0 AWG and larger. The conductors are cabled together and a binder tape is wrapped around the assembly. Aluminum interlocking armor is applied over the assembly. A black flame retardant sunlight resistant PVC jacket is applied over the armor. The jacket is available in other colors upon request, subject to economic order quantities.