ACSR/TW

Aluminum Conductor. Steel Reinforced. Trapezoidal Shaped Aluminum Strands.
Download Category Specifications:
PDF Excel Table

Application

  • Used for bare overhead transmission, and primary and secondary distribution.
  • Two design offerings: Equal Area or Equal Diameter when compared to standard round ACSR
  • Equal area designs allow comparable ampacity in a smaller diameter conductor when compared to a standard round ACSR.
  • Equal diameter designs allow more ampacity and strength in an equal diameter conductor when compared to a standard round ACSR.

Specifications

measurement
imperial metric
Select a set of products below for more information:
Conductor
No. of Conductors Size (AWG or kcmil) No. of Strands Nom. OD (mils) (mm) Nominal Total Weight (lbs/1000') (kgs/km) Allowable Ampacity
624383 1 1 411.4 KCMIL 411.4 KCMIL 16 16 722 18.36 532 791
365775 1 1 556.5 KCMIL 556.5 KCMIL 20 20 850 21.60 785 1168
617080 1 1 565.3 KCMIL 565.3 KCMIL 0 0 860 21.84 797 1186
617090 1 1 664.8 KCMIL 664.8 KCMIL 0 0 930 23.62 935 1392
618839 1 1 954 KCMIL 954 KCMIL 0 0 1061 26.95 1074 1598
510032 1 1 959.6 KCMIL 959.6 KCMIL 0 0 1110 28.19 1350 2009
624384 1 1 997.2 KCMIL 997.2 KCMIL 0 0 1108 28.14 1280 1905
617082 1 1 1158.4 KCMIL 1158.4 KCMIL 0 0 1200 30.48 1525 2270
617083 1 1 1233.6 KCMIL 1233.6 KCMIL 0 0 1245 31.62 1584 2357
624378 1 1 1443.7 KCMIL 1443.7 KCMIL 56 56 1338 33.99 1760 2620
335265 1 1 1622 KCMIL 1622 KCMIL 0 0 1420 36.07 2107 3135
624382 1 1 1780 KCMIL 1780 KCMIL 0 0 1445 36.70 2119 3153
617086 1 1 1926.9 KCMIL 1926.9 KCMIL 42 42 1549 39.37 2507 3730
617085 1 1 1533.3 KCMIL 1533.3 KCMIL 38 38 1380 35.05 1966 2926

Standards & References

  • ASTM B230 Aluminum 1350-H19 Wire for Electrical Purposes
  • ASTM B498 Zinc-Coated (Galvanized) Steel Core Wire for Use in Overhead Electrical Conductors
  • ASTM B500 Metallic Coated or Aluminum Clad Stranded Steel Core for Use in Overhead Electrical Conductors
  • ASTM B779 Shaped Wire Compact Concentric-Lay-Stranded Aluminum Conductors, Steel-Reinforced (ACSR/TW)

Construction

  • Aluminum 1350-H19 trapezoidal-shaped wires, concentrically stranded about a steel core. Standard core wire coating for ACSR is Class A galvanized (GA2).
  • Also available in zinc-5% aluminum-mischmetal alloy coating or aluminum-clad (AW)
  • Additional corrosion protection is available through the application of grease to the core or complete conductor.
  • Also available in non-specular